14 - 66
MELSEC-A
14 TROUBLESHOOTING
Division of
warning
Warning
code
Warning name
Description
Action at occurrence of warning
112
Illegal override
value
A value outside the range from 1 to 300 is
specified as an override value.
•
Setting “0”: Controlled to 100.
•
“301” or larger setting: Controlled to 300.
113
Outside new
torque value
range
A value outside the range from 1 to 500 is
specified as a new torque value.
Torque change is not carried out.
114
Below bias
speed
The command speed is smaller than the
starting bias speed.
Operation is made at the bias speed at start.
115
Illegal No. of
read/write data
The No. of read/write data of positioning data
No. 101 to 600 is outside the range from 1 to
100.
•
The warning is for the target axis.
•
Reading/writing is not made.
Common
116
Parameter
transmission
failure
When the PLC READY signal [Y1D] turned
from OFF to ON, parameter transmission to the
servo amplifier failed.
The warning is for the target axis.
300
Speed change
during
deceleration
A speed change request is issued during
deceleration and stop caused by turned OFF of
the JOG start signal.
Speed change is not made.
JOG
301
JOG speed limit
value
The new speed value in JOG operation
exceeds the JOG speed limit value.
•
If the JOG speed limit value is exceeded,
JOG operation continues at the JOG speed
limit value.
•
The “in speed limit flag” is turned ON while
the JOG speed limit is active.
401
Outside manual
pulse generator
input
magnification
The manual pulse generator 1 pulse input
magnification is “0” or equal to or larger than
“101.”
•
Input magnification
≥
101: 100
•
Input magnification “0”: 1
Manual
pulse
generator
402
Manual pulse
generator
selection 0
The manual pulse generator enable flag is set
when “manual pulse generator selection” in
detail parameter 1 is set at “0.”
Failure to start manual pulse generator
operation
Содержание A1SD75M1
Страница 2: ......
Страница 20: ...A 18 MEMO...
Страница 22: ...MEMO...
Страница 27: ...1 5 MELSEC A 1 PRODUCT OUTLINE MEMO...
Страница 42: ...1 20 MELSEC A 1 PRODUCT OUTLINE MEMO...
Страница 52: ...2 10 MELSEC A 2 SYSTEM CONFIGURATION MEMO...
Страница 111: ...5 21 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 115: ...5 25 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 123: ...5 33 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 127: ...5 37 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 167: ...5 77 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 193: ...5 103 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 276: ...5 186 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 332: ...7 18 MELSEC A 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO...
Страница 334: ...MEMO...
Страница 422: ...9 64 MELSEC A 9 MAIN POSITIONING CONTROL MEMO...
Страница 446: ...10 24 MELSEC A 10 ADVANCED POSITIONING CONTROL MEMO...
Страница 472: ...11 26 MELSEC A 11 MANUAL CONTROL MEMO...
Страница 576: ...12 104 MELSEC A 12 CONTROL AUXILIARY FUNCTIONS MEMO...
Страница 673: ...Appendix 5 MELSEC A APPENDICES Axis address mm inch degree pulse Axis address mm inch degree pulse...
Страница 679: ...Appendix 11 MELSEC A APPENDICES Initial value Axis 1 Axis 2 Axis 3 Remarks 0 0 0 1 1 0 0 0 0 0 300 0 0 0...
Страница 683: ...Appendix 15 MELSEC A APPENDICES Initial value Axis 1 Axis 2 Axis 3 Remarks 0 0 1 0 0 50 80 0 0 980...
Страница 691: ...Appendix 23 MELSEC A APPENDICES Initial value Axis 1 Axis 2 Axis 3 Remarks 0 0 0 0 0 50 80 0 0 0 0 0 980 4000 0...
Страница 745: ......