5 - 110
MELSEC-A
5 DATA USED FOR POSITIONING CONTROL
Servo amplifier
side parameter
Setting value, setting range
Setting value buffer
memory address
Item
No.
Abbre-
viation
Value set with peripheral
device
Value set with sequence
program
Default
value
Axis 1 Axis 2 Axis 3
Pr.122
Monitor output
mode
selection
No.22 –
Use prohibited (set the default initial value)
0001
H
122 272 422
Amplifier EMG selection
0 :
Valid
0
H
1 :
Invalid
1
H
Serial encoder cable selection
Pr.123
Option
function 1
No.23 *OP1
Use prohibited (set "0")
0000
H
123 273 423
Slight vibration suppression function selection
0 :
Invalid
0
H
1 :
Valid
1
H
Motor-less operation selection
0 :
Invalid
0
H
Pr.124
Option
function 2
No.24 *OP2
1 :
Valid
1
H
0000
H
124 274 424
* This parameter is made valid when the servo amplifier is powered OFF, then ON again after it has been transferred
from the AD75 to the servo amplifier.
Pr.123
Option function 1
Set the option function 1 (amplifier EMG selection).
•
Amplifier EMG selection
The external emergency stop signal EM1 can be made invalid.
Amplifier EMG selection
0: Valid
1: Invalid
H
0
0
0
Pr.124
Option function 2
Set the option function 2 (slight vibration suppression function selection,
motor-less operation selection).
•
Slight vibration suppression function selection
When "
Pr.108
Auto tuning" is set to "2: Invalid", the function to suppress
vibration at a stop can be made valid.
•
Motor-less operation selection
When motor-less operation is valid, signals can be output or the status displayed
without connection of the servomotor.
Slight viblation suppression function selection
0: Invalid
1: Valid
Motor-less operation selection
0: Invalid
1: Valid
H
0
0
Содержание A1SD75M1
Страница 2: ......
Страница 20: ...A 18 MEMO...
Страница 22: ...MEMO...
Страница 27: ...1 5 MELSEC A 1 PRODUCT OUTLINE MEMO...
Страница 42: ...1 20 MELSEC A 1 PRODUCT OUTLINE MEMO...
Страница 52: ...2 10 MELSEC A 2 SYSTEM CONFIGURATION MEMO...
Страница 111: ...5 21 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 115: ...5 25 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 123: ...5 33 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 127: ...5 37 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 167: ...5 77 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 193: ...5 103 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 276: ...5 186 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 332: ...7 18 MELSEC A 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO...
Страница 334: ...MEMO...
Страница 422: ...9 64 MELSEC A 9 MAIN POSITIONING CONTROL MEMO...
Страница 446: ...10 24 MELSEC A 10 ADVANCED POSITIONING CONTROL MEMO...
Страница 472: ...11 26 MELSEC A 11 MANUAL CONTROL MEMO...
Страница 576: ...12 104 MELSEC A 12 CONTROL AUXILIARY FUNCTIONS MEMO...
Страница 673: ...Appendix 5 MELSEC A APPENDICES Axis address mm inch degree pulse Axis address mm inch degree pulse...
Страница 679: ...Appendix 11 MELSEC A APPENDICES Initial value Axis 1 Axis 2 Axis 3 Remarks 0 0 0 1 1 0 0 0 0 0 300 0 0 0...
Страница 683: ...Appendix 15 MELSEC A APPENDICES Initial value Axis 1 Axis 2 Axis 3 Remarks 0 0 1 0 0 50 80 0 0 980...
Страница 691: ...Appendix 23 MELSEC A APPENDICES Initial value Axis 1 Axis 2 Axis 3 Remarks 0 0 0 0 0 50 80 0 0 0 0 0 980 4000 0...
Страница 745: ......