11 MANUAL CONTROL
11.3.4 Creating a program to enable/disable the manual pulse generator operation
A sequence program must be created to execute a manual pulse generator operation.
Consider the "required control data setting", "start conditions", "start time chart", and
"device settings" when creating the program.
The following shows an example when a manual pulse generator operation is started
for axis 1.
Required control data setting
The control data shown below must be set to execute a manual pulse generator
operation. The setting is carried out with the sequence program.
Buffer memory address
Setting item
Setting
value
Setting details
Axis 1 Axis 2 Axis 3
Cd.22
Manual pulse
generator enable
flag
1 (0)
Set "1: Enable manual pulse generator
operation". (Set "0: Disable manual pulse
generator operation" when finished with the
manual pulse generator operation.)
1167 1217 1267
Cd.23
Manual pulse
generator 1 pulse
input magnification
1
Set the manual pulse generator 1 pulse input
magnification.
1168
1169
1218
1219
1268
1269
* Refer to section "5.7 List of control data" for details on the setting details.
Conditions for enabling manual pulse generator operation
The following conditions must be satisfied to enable manual pulse generator
operation. The required conditions must also be assembled in the sequence
program, and the sequence program must be configured so the operation will not
start if the conditions are not fulfilled.
Device
Signal name
Signal state
Axis 1 Axis 2 Axis 3
All axes servo ON signal ON Servo operation possible
Y15
PLC READY signal
ON PLC CPU preparation completed
Y1D
AD75 READY signal
OFF AD75 preparation completed
X0
Axis stop signal
OFF Axis stop signal is OFF
Y13
Y14
Y1C
Start complete signal
OFF Start complete signal is OFF
X1
X2
X3
BUSY signal
OFF BUSY signal is OFF
X4
X5
X6
Error detection signal
OFF There is no error
XA
XB
XC
Interface
signal
M code ON signal
OFF M code ON signal is OFF
XD
XE
XF
Stop signal
OFF Stop signal is OFF
–
Upper limit (FLS)
ON Within limit range
–
External
signal
Lower limit (RLS)
ON Within limit range
–
Monitor
data
Servo ON
ON Servo ON is ON
Md.116
Servo
status:b1
Содержание A1SD75M1
Страница 2: ......
Страница 20: ...A 18 MEMO...
Страница 22: ...MEMO...
Страница 27: ...1 5 MELSEC A 1 PRODUCT OUTLINE MEMO...
Страница 42: ...1 20 MELSEC A 1 PRODUCT OUTLINE MEMO...
Страница 52: ...2 10 MELSEC A 2 SYSTEM CONFIGURATION MEMO...
Страница 111: ...5 21 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 115: ...5 25 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 123: ...5 33 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 127: ...5 37 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 167: ...5 77 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 193: ...5 103 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 276: ...5 186 MELSEC A 5 DATA USED FOR POSITIONING CONTROL MEMO...
Страница 332: ...7 18 MELSEC A 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO...
Страница 334: ...MEMO...
Страница 422: ...9 64 MELSEC A 9 MAIN POSITIONING CONTROL MEMO...
Страница 446: ...10 24 MELSEC A 10 ADVANCED POSITIONING CONTROL MEMO...
Страница 472: ...11 26 MELSEC A 11 MANUAL CONTROL MEMO...
Страница 576: ...12 104 MELSEC A 12 CONTROL AUXILIARY FUNCTIONS MEMO...
Страница 673: ...Appendix 5 MELSEC A APPENDICES Axis address mm inch degree pulse Axis address mm inch degree pulse...
Страница 679: ...Appendix 11 MELSEC A APPENDICES Initial value Axis 1 Axis 2 Axis 3 Remarks 0 0 0 1 1 0 0 0 0 0 300 0 0 0...
Страница 683: ...Appendix 15 MELSEC A APPENDICES Initial value Axis 1 Axis 2 Axis 3 Remarks 0 0 1 0 0 50 80 0 0 980...
Страница 691: ...Appendix 23 MELSEC A APPENDICES Initial value Axis 1 Axis 2 Axis 3 Remarks 0 0 0 0 0 50 80 0 0 0 0 0 980 4000 0...
Страница 745: ......