66
SPECIFICATIONS
1.4.18 Inverter operating status output signal (RUN, RUN2*, RUN3*, RY, RY2*, Y30*,
Y31*, Y32*, ALM, ALM2*, IPF*, Y91, OL, RBP, THP, FIN)
(common)
(1) Inverter operation ready signal (RY, RY2
*
)
and inverter running signal (RUN, RUN2
*
,
RUN3)
(*RY2, RUN2 are not available for
.)
(*RY2, RUN2, RUN3 are not available for
.)
1)
During V/F control, Advanced magnetic flux
vector control
*1
, General-purpose magnetic
flux vector control, Simple magnetic flux
vector control
*1
When the inverter is ready to operate, the output
of the operation ready signal (RY) is ON.
(It is also ON during inverter running.)
When the output frequency of the inverter rises to
or above [
Pr. 13 Starting frequency
], the output of
the inverter running signals (RUN, RUN2) is
turned ON. During an inverter stop or DC injection
brake operation, the output is OFF.
For the RUN3 signal, the output is ON while the
inverter is running and the start signal is ON. (For
the RUN3 signal, output is ON if the start
command is on even when a fault occurs or the
MRS signal is ON.)
The output is ON during DC injection brake
operation and OFF during an inverter stop.
*1
Advanced magnetic flux vector control can be set with
, General-purpose magnetic flux vector
control can be set with
and Simple magnetic
flux vector control can be set with
.
(*RUN2, RY2, Y30, Y31, Y32 are not available for
.)
(*RUN2, RUN3, RY2, Y30, Y31, Y32, ALM2, IPF are not available for
.)
common
F700
E700
D700
common
F700
E700 D700
common
A700
E700
E700
D700
F700
Power
supply
Output frequency
STF
RH
RY
RUN3
[
Pr. 13
]
Time
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
RUN
(RUN2)
DC injection brake
operation point
DC injection
brake
operation
Reset
processing
Output
Signal
Start
Signal
OFF
(during
stop)
Start
Signal ON
(during
stop)
Start
Signal ON
(during
operation)
Under DC
Injection
Brake
At Alarm
Occurrence
or MRS Signal ON
(output shutoff)
Automatic Restart after
Instantaneous Power Failure
Coasting
Restarting
Start
signal
ON
Start
signal
OFF
Start
signal
ON
Start
signal
OFF
RY
ON
ON
ON
ON
OFF
ON
*1
ON
RY2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
RUN
OFF
OFF
ON
OFF
OFF
OFF
ON
RUN2
OFF
OFF
ON
OFF
OFF
OFF
ON
RUN3
OFF
ON
ON
ON
ON
OFF
ON
OFF
ON
*1
This signal turns OFF during power failure or undervoltage.