(2) AM terminal calibration [C1(Pr. 901)]
Terminal AM is factory-set to provide a 10VDC output
in the full-scale status of the corresponding monitor
item. Calibration parameter [
C1 (Pr. 901)
] allows the
output voltage ratios (gains) to be adjusted according
to the meter scale. Note that the maximum output
voltage is 10VDC.
Connect a meter/frequency meter (DC voltmeter
10V) to across inverter terminals AM-5. (Note the
polarity. The terminal AM is positive.)
Set the monitor description in [
Pr. 158
] and operate
the inverter. (It is not necessary to connect the
motor.) Read [
C1
] and turn
to change the output
voltage, enabling the indicator/frequency meter to be
calibrated. When calibrating a monitor output signal,
which cannot adjust to a 100% value without an
actual load and a measurement equipment, set [
Pr.
54
= 21] (reference voltage output) and make
calibration. 10VDC is output from the terminal AM.
2.15.5 Signal selection and calibration of terminal AM0, AM1 (FR-A7AY)
[Pr. 307 to 309
,
311
,
312
,
323
,
324, C0(Pr. 900), C1(Pr.901)]
(A700)(F700)(E700)
Signal output from terminal AM0 (analog voltage output) and AM1 (analog current output) when the plug-in option FR-A7AY is
fitted to the inverter can be selected and calibrated.
* The setting is available for
when it has built-in option FR-A7AY installed.
A700
F700
AM
Inverter
DC10V
5
A700 F700 E700
[Pr. ]
Name
Initial
Value
Setting
Range
Description
307
Setting for zero
analog output
0%
0 to 100%
[
Pr. 309
= 0, 1] : Output signal value for zero analog output
When[
Pr. 309
= 10,11]: Analog output value for zero output signal
308
Setting for maximum
analog output
100%
0 to 100%
[
Pr. 309
= 0, 1] : Output signal value for maximum analog output
[
Pr. 309
=10, 11] : Analog output value for maximum output signal
309
Voltage/current
selection for analog
output signal
0
0
Output signal selection, calibration/adjustment method
Terminal AM0
Terminal AM1
Signal selection ( same signal is output from terminal AM0 and AM1) using [
Pr. 306
]
Full-scale calibration using [
C1 (Pr. 901)
]
Adjustment of output signal value using [
Pr. 307, Pr. 308
]
1
Selection of signal using [
Pr. 310
]
Full-scale calibration using [
C0 (Pr. 900)
]
Adjustment of output signal value using
[
Pr. 311, Pr. 312
]
Selection of signal using [
Pr. 306
]
Full-scale calibration using [
C1 (Pr. 901)
]
Adjustment of output signal value using
[
Pr. 307, Pr. 308
]
10
Signal selection ( same signal is output from terminal AM0 and AM1) using [
Pr. 306
]
Full-scale calibration using [
C1 (Pr. 901)
]
Adjustment of analog output value using [
Pr. 307, Pr. 308
]
11
Selection of signal using [
Pr. 310
]
Full-scale calibration using [
C0 (Pr. 900)
]
Adjustment of analog output value using
[
Pr. 311, Pr. 312
]
Selection of signal using [
Pr. 306
]
Full-scale calibration using [
C1 (Pr. 901)
]
Adjustment of analog output value using
[
Pr. 307, Pr. 308
]
311
Setting for zero
analog meter
voltage output
0%
0 to 100%
[
Pr. 309
= 1]: Output signal value for zero analog output
[
Pr. 309
= 11]: Analog output value for zero output signal
312
Setting for maximum
analog meter
voltage output
100%
0 to 100%
[Pr. 309 = 1] : Output signal value for maximum analog output
[
Pr. 309
= 11]: Analog output value for maximum output signal
323
AM0 0V
adjustment
1000%
900 to
1100%
The meter connected to terminal AM0 can be adjusted to stop at 0.
324
AM1 0mA
adjustment
1000%
900 to
1100%
The meter connected to terminal AM1 can be adjusted to stop at 0.
C0(900)
FM terminal
calibration
—
—
Scale of the connected meter to terminal AM0 can be calibrated.
C1(901)*
AM terminal
calibration
—
—
Scale of the connected meter to terminal AM1 can be calibrated.