93
1
S
PECIFI
C
A
T
IONS
SPECIFICATIONS
4) FR-A7AZ
(2) 16Bit digital input connection example
1) Relay contact signal input
*4
(sink logic
*3
)
*1
Use terminals SD or PC on the inverter.
*2
AY41 type unit requires 24VDC power.
Example of connection with the output module (AY41
type) of Mitsubishi programmable controller. Refer to the
output module manual for details of the output module.
*3
The control logic is the same as that of the inverter
(factory-set to sink). When the logic of the inverter is
changed to source, the option logic also switches to
source. To change the control logic, refer to page 40.
*4
As the input signals are at low level, use two parallel
micro signal contacts or a twin contact for relay contact
inputs to prevent a contact fault.
*5
A transistor of the following specifications should be
selected for the open collector signal:
Electrical characteristics of the transistor used
• Ic
≥
10mA
• Leakage current: 100
µ
A or less
• VCE
≥
30V
• When Ic
≥
10mA, VCE(sat) voltage 3V or less.
Terminal
Symbol
Terminal Name
Rating, etc.
Description
Refer to
Page
DA1
Bipolar analog output
terminal
Output voltage : -10 to +10VDC
Connect a DC indicator (
±
10VDC).
Change the monitor to be output with [
Pr.838
].
6
High resolution input
terminal
Frequency setting resolution : 0.01Hz/0
to 60Hz (-10 to +10V)(0.015Hz/0 to 60Hz
when option is not mounted)
Torque setting resolution : 0.024%/0 to
100% (-10 to +10V)(0.1%/0 to 100%
when option is not mounted)
Input resistance : 10k
Ω
Maximum input voltage :
±
20VDC
Terminal for 0 to
±
10VDC high resolution (16bit)
analog voltage input. Use [
Pr. 406
] High
resolution analog input selection to select
terminal function.
5
Common terminal
―
Common terminal of terminal 6 and the DA1.
—
TH1
Thermistor input 1
―
Enter thermistor output signal for the motor dedi-
cated to vector control (SF-V5RU)
TH2
Thermistor input 2
SW2
Thermistor calibration
status switch
When calibrating at installation, change the
switch to place the inverter in calibration status.
2) Open collector signal input
*5
(Sink logic
*3
)
A700
F700
E700
DY
FR-A7AX
SD
*1
X0
X1
X2
X3
X4
X5
X6
X7
X8
X9
X10
X11
X12
X13
X14
X15
Unit's place
Ten's place
Hundred's place
Thousand's place
Inverter
FR-A7AX
Unit's place
Ten's place
Hundred's place
Thousand's place
Reading command
QY41 type
transistor
output unit
*2
Inverter
X0
DY
PC
*1
*2
B01,B02
A5
A01,A02
B16
B14
B13
B11
B9
B7
B5
B6
B8
B10
B12
B15
B17
B18
B19
B20
X1
X2
X3
X4
X5
X6
X7
X9
X10
X11
X12
X13
X14
X15
X8
Micro signal contacts
Twin contacts