333
PARAMETER
2
P
ARAM
ETE
R
(10) DC feeding mode1 [Pr. 30 = 10, 11]
Setting [
Pr. 30
= 10, 11] enables DC power supply
operation. Built-in brake transistor control is valid.
Leave the AC power supply connection terminals R/
L1, S/L2, and T/L3 open and connect the DC power
supply to terminals P/
+
and N/-. Also, remove
jumpers across terminals R/L1 and R/1/L11 and
across terminals S/L2 and S1/L21. And connect
terminals R1/L11 and S1/L21 to terminal P/
+
and N/-.
The diagram below is a connection example.
(11) DC feeding mode 2 [Pr. 30 = 20, 21]
When [
Pr. 30
= 20, 21], operation is performed with
AC power normally and with DC power such as
battery at power failure. Built-in brake transistor
control is valid.
Connect the AC power supply to terminal R/L1, S/L2,
and T/L3 and connect the DC power supply to
terminal P/
+
and N/-. Also, remove jumpers across
terminal R/L1 and R/1/L11 and across terminal S/L2
and S1/L21. And connect terminals R1/L11 and S1/
L21 to terminal P/
+
and N/-.
Turning ON the DC feeding operation permission
signal (X70) enables DC power supply operation.
The following shows the connection diagram when
switching to a DC power using inverter power failure
detection.
A700
R/L1
S/L2
T/L3
U
V
W
P/+
N/-
IM
STF
STR
R1/L11
S1/L21
10
2
2
3
1
5
(+)
(-)
MC
Inrush
current
limit circuit
DC power
Forward rotation start
Reverse rotation start
Contact input common
Frequency command
Frequency setting
potentiometer
1/2W1k
Ω
Earth
(Ground)
Inverter
SD
A700
DC power
MCCB
R/L1
S/L2
T/L3
U
V
W
P/+
N/-
IM
STF
STR
X70
X71
SD
R1/L11
S1/L21
Earth
(Ground)
10
2
2
3
1
5
(+)
(-)
*1
MC
Three-phase AC
power supply
DC feeding permission signal
DC feeding cancel signal
Contact input common
Reverse rotation start
Forward rotation start
*1
Inverter
Inrush
current
limit circuit
Frequency command
Frequency setting
potentiometer
1/2W1k
Ω
SE
Y85
MC
*2
24VDC
DC feeding signal
*1
Assign the function using [
Pr. 178 to 189 input terminal function selection
].
*2
Assign the function using [
Pr. 190 to 196 output terminal function selection
].