82
SPECIFICATIONS
(3) PU connector communication system
configuration and wiring
Using the PU connector, you can perform
communication operation from a personal computer
etc.
When the PU connector is connected with a
personal, FA or other computer by a communication
cable, a user program can run and monitor the
inverter or read and write to parameters.
When performing RS-485 communication with
multiple inverters, use the RS-485 terminal. (Refer to
page 83)
1) System configuration
(a) Refer to the following when fabricating the
cable on the user side.
Examples of product available on the market
(as of February, 2008)
2) Connection with RS-485 computer
Product
Type
Maker
1)
10BASE-T
Cable
SGLPEV-T
0.5mm
×
4P
*1
Mitsubishi Cable Industries,
Ltd.
2)
RJ-45
Connector
5-554720-3
Tyco Electronics
Corporation
*1
Do not use pins No. 2, 8 of the 10BASE-T cable.
common
PU
connector
Inverter
Station 0
Computer
PU
connector
Inverter
Station 0
Computer
10BASE-T cable 1)
10BASE-T cable 1)
RS-232C-RS-485
converter
RS-232C
cable
RS-485
interface/
terminals
RJ-45
connector
RJ-45
connector 2)
Maximum
15m
RS-232C
connector
Computer Side Terminals
Send data
Send data
Receive data
Receive data
Description
Frame ground
Signal ground
Clear to send
Clear to send
Request to send
Request to send
SDB
SDA
RDB
RDA
Signal name
FG
SG
CSB
CSA
RSB
RSA
RDB
RDA
SDB
SDA
PU connector
SG
Inverter
*
0.2mm
2
or more
Cable connection and signal direction
10BASE-T cable
RS-485 terminal
* Make connections in accordance with the manual of the
computer used.
Fully check the terminal numbers of the computer since
these vary with the model.
Содержание FR-A700 Series
Страница 245: ...279 2 PARAMETER PARAMETER MEMO ...
Страница 440: ...474 PARAMETER MEMO ...
Страница 522: ...556 SELECTION MEMO ...