254
PARAMETER
2) FR-F700 series
Select the inverter control method from V/F
control and Simple magnetic flux vector control.
3) FR-E700 series
Select the inverter control method from V/F
control, Advanced magnetic flux vector control,
General-purpose magnetic flux vector control.
You can set the thermal characteristic of the
electronic thermal for the second motor by setting
[
Pr. 450
≠
9999
]. At this time, control method does
not change.(Depends on the settings of [
Pr. 80, 81,
800
])
4) FR-D700 series
Select the inverter control method from V/F
control and General-purpose magnetic flux vector
control.
You can set the thermal characteristic for the
second motor by setting [
Pr. 450
≠
9999
]. At this
time, control method does not change. (Depends
on the settings of [
Pr. 80
])
[
Pr.
]
Name
Initial
Value
Setting Range
Description
80
Motor capacity
9999
55K or less
0.4 to 55kW
Simple magnetic flux vector control
Set the applied motor capacity.
75K or more
0 to 3600kW
9999
V/F control
[
Pr.
]
Name
Initial
Value
Setting Range
Description
80
Motor capacity
9999
0.1 to 15kW
Set the applied motor capacity.
9999
V/F control
81
Number of motor poles
9999
2, 4, 6, 8, 10
Set the number of motor poles.
9999
V/F control
450 Second applied motor
9999
0, 1
Set when using the second motor.
9999
Function invalid ([
Pr. 71
] is valid.)
800
Control method
selection
20
20
V/F control *
Advanced magnetic flux vector control
30
General-purpose magnetic flux vector
control
* When [
Pr.80 Motor capacity = 9999
] or [
Pr.81 Number of motor poles = 9999
], control method is V/F control regardless of [
Pr.800
] setting.
[
Pr. 80, 81
]
[
Pr. 800
] Setting
Control Method
Other than 9999
20
([
Pr. 800
] initial value)
Advanced magnetic flux vector control
30
General-purpose magnetic flux vector control
9999
—
*
V/F control
* Control method is V/F control regardless of the setting value of [
Pr. 800
] when [
Pr. 80 Motor capacity
= 9999] or [
Pr. 81 Number of motor
poles =
9999].
[
Pr.
]
Name
Initial
Value
Setting Range
Description
80
Motor capacity
9999
0.1 to 7.5kW
General-purpose magnetic flux vector control
Set the applied motor capacity.
9999
V/F control
450 Second applied motor
9999
0, 1
Set when using the second motor.
9999
Function invalid ([
Pr. 71
] is valid.)