463
PARAMETER
2
P
ARAM
ETE
R
• Description of normal response
z
Write holding register data (H06 or 06)
Can write the description of 1) system
environment variables and 4) inverter parameters
assigned to the holding register area (refer to the
register list (page 468)).
Query message
Normal response (Response message)
•Query message setting
• Description of normal response
1) to 4) (including CRC check) of the normal
response are the same as those of the query
message. For broadcast communication, no
response is returned in reply to a query.
Therefore, the next query must be made when
the inverter processing time has elapsed after
the previous query.
Message
Setting Description
5)Byte Count
The setting range is H02 to H14 (2 to 20).
Twice greater than the No. of Point specified at 4) is set.
6) Data
The number of data specified at 4) is set. Data are read in order of Hi byte and Lo byte, and set in
order of starting address data, starting a 1 data, starting a 2 data, ...
[Example] To read the register values of 41004 ([
Pr. 4
]) to 41006 ([
Pr. 6
]) from the slave address 17 (H11).
Query message
Normal response (Response message)
Read value
Register 41004 ([Pr. 4]): H1770 (60.00Hz)
Register 41005 ([Pr. 5]): H0BB8 (30.00Hz)
Register 41006 ([Pr. 6]): H03E8 (10.00Hz)
Slave Address
Function
Starting Address
No. of Points
CRC Check
H11
(8bit)
H03
(8bit)
H03
(8bit)
HEB
(8bit)
H00
(8bit)
H03
(8bit)
H77
(8bit)
H2B
(8bit)
Slave
Address
Function
Byte Count
Data
CRC Check
H11
(8bit)
H03
(8bit)
H06
(8bit)
H17
(8bit)
H70
(8bit)
H0B
(8bit)
HB8
(8bit)
H03
(8bit)
HE8
(8bit)
H2C
(8bit)
HE6
(8bit)
1) Slave
Address
2) Function
3) Register
Address
4) Preset Data
CRC Check
(8bit)
H06
(8bit)
H
(8bit)
L
(8bit)
H
(8bit)
L
(8bit)
L
(8bit)
H
(8bit)
1) Slave
Address
2) Function
3) Register
Address
4) Preset Data
CRC Check
(8bit)
H06
(8bit)
H
(8bit)
L
(8bit)
H
(8bit)
L
(8bit)
L
(8bit)
H
(8bit)
Message
Setting Description
1) Slave address
Set the address to which a message will be sent. Setting of address 0 enables broadcast
communication.
2) Function
Set H06.
3) Register Address
Set the address of the holding register to which data will be written.
Register address = Holding register address (decimal) - 40001
For example, setting of register address 0001 writes data to the holding register address 40002.
4) Preset Data
Set the data that will be written to the holding register. The written data is always 2 bytes.
[Example] To write 60Hz (H1770) to 40014 (running frequency RAM) at slave address 5 (H05).
Query message
Normal response (Response message)
Same data as the query message
Slave Address
Function
Register Address
Preset Data
CRC Check
H05
(8bit)
H06
(8bit)
H00
(8bit)
H0D
(8bit)
H17
(8bit)
H70
(8bit)
H17
(8bit)
H99
(8bit)