515
SELECTION
S
E
LECTION
3
Overview of the guideline (excerpt)
5.Other references
(1) Contract power
If the "contract power" is not determined at the point of a consumption contract between an electric power
company and a consumer or more than one consumer and will be determined later, the contract power shall be
as defined below:
1) The contract facility power applies to consumers to whom the "real amount system" of the industrial power
of high-voltage power A or less than 500kW contract power is applied.
2) when there are more than one contract power such as time zone-based regulation contract, the largest
contract power applies among the contract powers.
(2) Maximum operation ratio of harmonic generating equipment
The "maximum operation ratio of harmonic generating equipment" indicates the ratio of the maximum actual
operation capacity (average during 30 minutes) to the sum of capacities of the harmonic generating equipment.
Maximum outgoing harmonic current values per 1kW contract power
(Unit: mA/kW)
Received
Power Voltage
5th
7th
11th
13th
17th
19th
23rd
Over 23rd
6.6kV
3.5
2.5
1.6
1.3
1.0
0.9
0.76
0.70
22
1.8
1.3
0.82
0.69
0.53
0.47
0.39
0.36
33
1.2
0.86
0.55
0.46
0.35
0.32
0.26
0.24
66
0.59
0.42
0.27
0.23
0.17
0.16
0.13
0.12
77
0.50
0.36
0.23
0.19
0.15
0.13
0.11
0.10
110
0.35
0.25
0.16
0.13
0.10
0.09
0.07
0.07
154
0.25
0.18
0.11
0.09
0.07
0.06
0.05
0.05
220
0.17
0.12
0.08
0.06
0.05
0.04
0.03
0.03
275
0.14
0.10
0.06
0.05
0.04
0.03
0.03
0.02