468
PARAMETER
1) [
Pr. 343 Communication error count
]
You can check the cumulative number of
communication errors by reading [
Pr. 343
]. The
number of communication errors is temporarily
stored into the RAM.
As it is not stored into the EEPROM, performing a
power supply reset or inverter reset clears the
value to 0.
2) Output signal LF alarm output (communication
error warnings)
During a communication error, the alarm signal
(LF signal) is output by open collector output.
Assign the used terminal with any of [
Pr. 190 to Pr.
196 Output terminal function selection
].
(6) Modbus registers
z
System environment variable
Alarm data
Reply data
Master
Slave
0
Signal LF
Normal data
Alarm data
Alarm data
1
2
OFF
ON
OFF
OFF
ON
Not increased
Turns OFF when normal data is received
Alarm data :
Normal data
Reply data
Communication error count is increased in
synchronization with leading edge of LF signal
Data resulting in
communication error.
Communication
Error count
[
Pr. 343
]
Register
Definition
Read/Write
Remarks
40002
Inverter reset
Write
Any value can be written
40003
Parameter clear
Write
Set H965A as a written value.
40004
All parameter clear
Write
Set H99AA as a written value.
40006
Parameter clear
*1
Write
Set H5A96 as a written value.
40007
All parameter clear
*1
Write
Set HAA99 as a written value.
40009
Inverter status/control input instruction
*2
Read/write
See below.
40010
Operation mode/inverter setting
*3
Read/write
See below.
40014
Running frequency (RAM value)
Read/write
According to the [
Pr. 37, Pr. 144
] settings, the
frequency and selectable speed are in
1r/min increments.
40015
Running frequency (EEPROM value)
Write
*1
The communication parameter values are not cleared.
*2
For write, set the data as a control input instruction. For read, data is read as an inverter operating status.
*3
For write, set data as the operation mode setting. For read, data is read as the operation mode status.
*1
The signal within parentheses is the default setting. Descriptions change according to the [
Pr. 180 to Pr. 189 Input terminal
function selection
].
Each assigned signal is valid or invalid depending on NET. (Refer to page
*2
The signal within parentheses is the default setting. Descriptions change according to the [
Pr. 190 to Pr. 196 Output terminal
function selection
].
*3
These are not available for
.
*4
These are not available for
.
<Inverter status/control input instruction>
Bit
Definition
Control input instruction
Inverter status
0
Stop command
RUN (inverter running)
*2
1
Forward rotation command
Forward running
2
Reverse rotation command
Reverse running
3
RH (high speed command)
*1
SU (up-to-frequency)
*2
4
RM (middle speed command)
*1
OL (overload)
*2
5
RL (low speed command)
*1
IPF (instantaneous power failure)
*2*3*4
6
JOG (Jog operation selection)
*1*3*4
FU (frequency detection)
*2
7
RT (second function selection)
*1
ABC1 (fault)
*2
8
AU (current input selection)
*1
ABC2 (—)
*2*3*4
9
CS (selection of automatic restart
after instantaneous power failure)
*1*3*4
0
10
MRS output stop
*1
0
11
STOP (start self-holding)
*1*3*4
0
12
RES (reset)
*1*4
0
13
0
0
14
0
0
15
0
Fault occurrence
E700
D700
The restrictions depending on the operation
mode changes according to the computer
link specifications.
<Operation mode/inverter setting>
Mode
Read Value
Written
Value
EXT
H0000
H0010
PU
H0001
—
EXT
JOG
H0002
—
PU
JOG
*4
H0003
—
NET
H0004
H0014
PU+
EXT
H0005
—