(3) Connection diagram
(4) I/O signals and parameter setting
Set "40 to 43" in [
Pr. 128
] to perform dancer control.
(Disable PID output interruption function ([
Pr. 575
=
9999]) during dancer control.)
Set "14" in any of [
Pr. 178 to
Pr. 184
(
input terminal
function selection
)] to assign PID control selection
signal (X14) to turn the X14 signal ON.
When the X14 signal is not assigned, only the
Pr. 128
setting makes dancer control valid.
Input the main speed command (External, PU,
Network). The main speed command in any
operation mode can be input. (Note that terminal 4
can not be used as the main speed command.)
(Terminal 2 is not available for speed control when
[
Pr. 561 PTC thermistor protection level
≠
9999] in
. Terminal 2 functions as a PTC thermistor
input terminal.)
Input the set point using [
Pr. 133
], then input the
measured value signal (dancer roller position
detection signal) across terminal 4 and 5 of the
inverter.
When [
Pr. 128
] = "0" or X14 signal is OFF, normal
inverter operation is performed without dancer
control.
Turning ON/OFF of bit of the terminal, to which X14
signal is assigned through network as RS-485
communication, enables dancer control.
Power
supply
MCCB
Inverter
Forward rotation
Reverse rotation
PID control selection
Main speed command
setting potentiometer
*1
R/L1
S/L2
T/L3
STF
STR
MRS(X14)
*3
SD
10
2
5
4
*4
U
V
W
*2
(FUP)RUN
*2 *5
(FDN)FU
SE
Motor
IM
Upper limit
Lower limit
Output signal common
Feedback value of
dancer roll position
y
Sink logic
y
Pr. 128 =
41
y
Pr. 183 =
14
y
Pr. 190 =
15
y
Pr. 191 =
14
*5
y
Pr. 192 =
16
*1
The main speed command differs according to each
operation mode (external, PU, communication)
*2
The used output signal terminal changes depending on
the
Pr. 190 to Pr. 192 (output terminal selection)
setting.
has only one open collector output terminal.
*3
The used input signal terminal changes depending on the
Pr. 178 to Pr. 184(input terminal selection)
setting.
*4
The AU signal need not be input.
*5
Available only in
.
D700
E700
D700
Signal
Terminal Used
Function
Description
Parameter Setting
In
put
X14
Depending on
[
Pr. 178
to
Pr. 184
]
PID control
selection
Turn ON X14 signal to perform dancer
control.
Set 14 in any of [
Pr. 178 to Pr. 184
].
4
4
Measured value
input
Input the signal from the dancer roller
detector (measured value signal).
[
Pr.128 =
40, 41, 42, 43]
4 to 20mA... 0 to 100%
[
Pr.267
= 0]
*2
0 to 5V........ 0 to 100%
[
Pr.267
= 1]
0 to 10V...... 0 to 100%
[
Pr.267
= 2]
Ou
tp
u
t
FUP
Depending on
[
Pr. 190
to
Pr. 192
]
Upper limit
output
Output to indicate that the measured
value signal exceeded the maximum
value
[
Pr. 131
].
[
Pr.128 =
40, 41, 42, 43]
[
Pr.131 =
9999]
Set 15 or 115 in any of [
Pr. 190
to
Pr. 192
].
FDN
Lower limit
output
Output when the measured value signal
falls below the minimum value [
Pr. 132
].
[
Pr.128 =
40, 41, 42, 43]
[
Pr.132
≠
9999]
Set 14 or 114 in any of [
Pr. 190
to
Pr. 192
].
RL
Forward
(reverse) rotation
direction output
Output is "ON" when the output
indication of the parameter unit is
forward rotation (FWD) and "OFF" when
reverse rotation (REV) or stop (STOP).
Set 16 or 116 in any of [
Pr. 190
to
Pr. 192
].
PID
During PID
control activated
Turns ON during PID control.
Set 47 or 147 in any of [
Pr. 190
to
Pr. 192
].
SE
SE
Output terminal
common
Common terminal for open collector
output terminal.
*1
When the X14 signal is not assigned, only the [
Pr. 128
= 40 to 43] setting makes dancer control valid.
*2
The shaded area indicates the parameter initial value.
*3
When 100 or larger value is set in any of
Pr. 190 to Pr. 192 (output terminal function selection)
, the terminal output has negative logic.
(For details, Refer to page 61)