361
PARAMETER
2
P
ARAM
ETE
R
(1) Energy saving monitor list
The following items are monitored by the power
saving monitor [
Pr. 52, Pr. 54, Pr. 158
= 50].
Only 1) power saving and 3) power saving average
value can be output to [
Pr. 54
] (terminal FM) and [
Pr.
158
] (terminal AM)).
The following items are monitored by the power saving monitor [
Pr. 52
= 51]. The monitor value of the cumulative monitor can be shifted to
the right with [
Pr. 891 Cumulative power monitor digit shifted times
] .
Energy saving
Monitor Item
Description and Calculation Formula
Increments
Parameter Setting
[Pr. 895] [Pr. 896] [Pr. 897] [Pr. 899]
1)
Power saving
Difference between the estimated value of power
necessary for commercial power supply operation and the
input power calculated by the inverter
Power during commercial power supply operation - input
power monitor
0.01kW/
0.1kW
*3
9999
—
9999
—
2)
Power saving rate
Ratio of power saving on the assumption that power
during commercial power supply operation is 100%
100
0.1%
0
Ratio of power saving on the assumption that [
Pr. 893
] is 100%.
100
1
3)
Average power
saving value
Average value of power saving amount per hour during the
set time ([
Pr. 897
])
0.01kWh/
0.1kWh
*3
9999
9999
0 to
1000h
4)
Average power
saving rate
Average ratio of power saving value on the assumption
that the value during commercial power supply operation
is 100%
0.1%
0
Ratio of power saving average value on the assumption
that [
Pr. 893
] is100%.
1
5)
Average power
saving amount
Average power saving value represented in terms of charge
3) Average power saving value [
Pr. 896
]
0.01/0.1
*3
—
0 to 500
1) Power saving
Power during commercial power supply operation
1) Power saving
[
Pr. 893
]
(1) Power saving
t)
100
[
Pr. 897
]
(2) Power saving rate
t)
100
[
Pr. 897
]
3) Average power saving value
100
[
Pr. 893
]
Energy Saving
Monitor Item
Description and Calculation Formula
Increments
Parameter Setting
[Pr. 895] [Pr. 896] [Pr. 897] [Pr. 899]
6)
Power saving
amount
Power saving is added up per hour.
(1) Power saving
t)
0.01kWh/
0.1kWh
*1*2*3
—
9999
—
9999
7)
Power saving
amount charge
Power saving amount represented in terms of charge
6) Power saving amount
[
Pr. 896
]
0.01/0.1
*1*3
—
0 to 500
8)
Annual power saving
amount
Estimated value of annual power saving amount
24
365
0.01kWh/
0.1kWh
*1*2*3
—
9999
0 to
100%
9)
Annual power saving
amount charge
Annual power saving amount represented in terms of charge
8)Annual power saving amount
[
Pr. 896
]
0.01/0.1
*1*3
—
0 to 500
6) Power saving amount
Operation time during power
saving accumulation
[
P.899
]
100
*1
For communication (RS-485 communication, communication option), the display increments are 1. For example, 10.00kWh
indicates that communication data is 10.
*2
When using the parameter unit (FR-PU04/FR-PU07), kW is displayed.
*3
The increments vary according to the inverter capacity.
(55K or less/75K or more)
*4
Since four digits are displayed on the operation panel (FR-DU07), the value is displayed in 0.1 increments when a monitor
value in 0.01 increments exceeds 99.99, then rounded up to 100.0. The maximum display is 9999.
*5
Since five digits are displayed on the parameter unit (FR-PU04/FR-PU07), the value is displayed in 0.1 increments when a
monitor value in 0.01 increments exceeds 999.99, then rounded up to 1000.0. The maximum display is 99999.
*6
When [
Pr. 898 Power saving cumulative monitor clear
= 9999], the maximum value of communication (RS-485 communication, communication
option) is 65535. The upper limit of 0.01 increments monitor is 655.35 and that of 0.1 increments monitor is 6553.5.