455
PARAMETER
2
P
ARAM
ETE
R
[Special monitor selection No.]
Refer to page 346 for details of the monitor description
*1
The setting depends on the inverter capacity. (55K or less/75K or more)
*2
Input terminal monitor details
*3
Output terminal monitor details
Data
Description
Increments
H01
Output frequency/speed
*11
0.01Hz/1
Output frequency/speed
*12
0.01Hz/
1(0.001)
H02
Output current
0.01A/
0.1A
*1
H03
Output voltage
0.1V
H05
Frequency setting/speed
*11
0.01Hz/1
Frequency setting/speed
*12
0.01Hz/
1(0.001)
H06
*9*10
Running speed
1r/min
H07
*8*10
Motor torque
0.1%
H08
Converter output voltage
0.1V
H09
Regenerative brake duty
0.1%
H0A
Electronic thermal relay function load factor
0.1%
H0B
Output current peak value
0.01A/0.1A
*1
H0C
Converter output voltage peak value
0.1V
H0D
*9*10
Input power
0.01kWh/
0.1kW
*1
H0E
Output power
0.01kWh/
0.1kW
*1
H0F
Input terminal status
*2
—
H10
Output terminal state
*3
—
H11
*9*10
Load meter
0.1%
H12
*8*9*10
Motor excitation current
0.01A/
0.1A
*1
A700 F700
E700 D700
A700 F700
E700 D700
H13
*8*9*10
Position pulse
—
H14
Cumulative energization time
1h
H16
*8*9*10
Orientation status
—
H17
Actual operation time
1h
H18
Motor load factor
0.1%
H19
Cumulative power
1kWh
H20
*8*9*10
Torque command
0.1%
H21
*8*9*10
Torque current command
0.1
H22
*8*9*10
Motor output
0.01kWh/
0.1kW
*1
H23
*8*9*10
Feedback pulse
—
H32
*9*10
Power saving effect
Variable
H33
*9*10
Cumulative saving power
Variable
H34
PID set point
0.1%
H35
PID measured value
0.1%
H36
PID deviation
0.1%
H3A
*8*10
Option input terminal status 1
*4
—
H3B
*8*10
Option input terminal status 2
*5
—
H3C
*8*10
Option output terminal status 2
*6
—
H3D
*7*8
Motor thermal load factor
0.1%
H3E
*7*8
Inverter thermal load factor
0.1%
H3F
*7*8*9
Cumulative power 2
0.01kWh
H40
*7*8*9
PTC thermistor resistance
0.01k
Ω
Data
Description
Increments
b15
b0
—
—
—
—
CS
RES
STOP
MRS
JOG
RH
RM
RL
RT
AU
STR
STF
b15
b0
—
—
—
—
—
RES
—
MRS
—
RH
RM
RL
—
—
STR
STF
b15
b0
—
—
—
—
—
—
—
—
—
RH
RM
RL
—
—
STR
STF
A700
F700
E700
D700
b15
b0
—
—
—
—
—
—
—
—
—
ABC2
ABC1
FU
OL
IPF
SU
RUN
b15
b0
—
—
—
—
—
—
—
—
—
—
ABC
FU
—
—
—
RUN
b15
b0
—
—
—
—
—
—
—
—
—
—
ABC
—
—
—
—
RUN
A700
F700
E700
D700
*4
Details of option input terminal monitor 1 (input terminal status of FR-A7AX)-all terminals are OFF when an option is not fitted
b15
b0
X15
X14
X13
X12
X11
X10
X9
X8
X7
X6
X5
X4
X3
X2
X1
X0
*5
Details of option input terminal monitor 2 (input terminal status of FR-A7AX)-all terminals are OFF when an option is not fitted
b15
b0
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
DY
*6
Details of option output terminal monitor (output terminal status of FR-A7AY/A7AR)--all terminals are OFF when an option is not fitted.
b15
b0
—
—
—
—
—
—
RA3
RA2
RA1
Y6
Y5
Y4
Y3
Y2
Y1
Y0