2.20.11 Speed smoothing control [Pr.653]
(E700)(D700)
Vibration due to mechanical resonance influences the inverter control, causing the output current (torque) unstable. In this
case, the output current (torque) fluctuation can be reduced to ease vibration by changing the output frequency.
(1) Control block diagram
(2) Setting method
If vibration due to mechanical resonance occurs, set 100% in [
Pr. 653
], run the inverter at the frequency which generates
maximum vibration and check if the vibration will be reduced or not after several seconds.
If effect is not produced, gradually increase the [
Pr. 653
] setting and check the effect repeatedly until the most effective value
is set in [
Pr. 653
].
If vibration becomes large by increasing the [
Pr. 653
] setting, gradually decrease the [
Pr. 653
] setting than 100% to check the
effect in a similar manner. (Depending on the machine, vibration may not be reduced enough or an effect may not be
produced.)
E700 D700
[Pr.]
Name
Initial
Value
Setting
Range
Description
653
Speed smoothing control
0
0 to 200%
Increase or decrease the value using 100% as reference to
check an effect.
V/F control
Torque current
Frequency output
Voltage output
+
-
Speed smoothing control
[
Pr.653
]
Acceleration/deceleration
processing
Output frequency
Speed
command