168
PA
R
A
M
E
T
E
R
2
168
PARAMETER
PARAMETER
2.1.3
FR-E700
For simple variable-speed operation of the inverter, the initial
setting of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational
specifications. Parameter setting, change and check can be
made from the operation panel.
•
indicates simple mode parameters. (initially set to
extended mode)
• The parameters marked with
in the table allow
its setting to be changed during operation even if "0"
(initial value) is set in [
Pr. 77 Parameter write selection
].
• Symbols in the table indicate parameters which
function when an option is mounted.
••••FR-A7AX E kit,
••••FR-A7AY E kit,
••••FR-A7AR E kit,
••••FR-A7NC E kit,
••••FR-A7ND E kit,
••••FR-A7NL E kit,
••••FR-A7NP E kit
• These instruction codes are used for parameter read
and write by using Mitsubishi inverter protocol with the
RS-485 communication.
• Symbols in the control mode-based correspondence table
indicate the following;
{
: Usable parameter
×
: Unusable parameter
• Symbols in the parameter copy, parameter clear, and all
parameter clear columns indicate the following;
{
: Valid
×
: Invalid
Fun
ct
io
n
[Pr.]
Name
Setting Range
Minimum Setting
Increments
Initial Value
Refer to
Page
[Pr.]
Option
Instruction Code
Control Mode-based Correspondence
Table
P
a
ra
m
et
er
Copy
P
a
ra
m
et
er
C
lear
All
P
a
ra
me
te
r
C
lear
R
ead
Wri
te
Ext
en
d
ed
V/F control
Advanced
magnetic
flux vector
control
General-
purpose
magnetic-
flux vector
control
Ba
si
c f
u
nct
ions
0
Torque boost
0 to 30%
0.1%
6/4/3/2%
0
00
80
0
{
×
×
{
{
{
1
Maximum frequency
0 to 120Hz
0.01Hz
120Hz
1
01
81
0
{
{
{
{
{
{
2
Minimum frequency
0 to 120Hz
0.01Hz
0Hz
2
02
82
0
{
{
{
{
{
{
3
Base frequency
0 to 400Hz
0.01Hz
60Hz
3
03
83
0
{
×
×
{
{
{
4
Multi-speed setting (high speed)
0 to 400Hz
0.01Hz
60Hz
4
04
84
0
{
{
{
{
{
{
5
Multi-speed setting (middle speed)
0 to 400Hz
0.01Hz
30Hz
5
05
85
0
{
{
{
{
{
{
6
Multi-speed setting (low speed)
0 to 400Hz
0.01Hz
10Hz
6
06
86
0
{
{
{
{
{
{
7
Acceleration time
0 to 3600/ 360s
0.1/0.01s
5/10/15s
7
07
87
0
{
{
{
{
{
{
8
Deceleration time
0 to 3600/ 360s
0.1/0.01s
5/10/15s
8
08
88
0
{
{
{
{
{
{
9
Electronic thermal O/L relay
0 to 500A
0.01A
Rated inverter
current
9
09
89
0
{
{
{
{
{
{
DC inj
e
ct
ion
brake
10
DC injection brake operation frequency
0 to 120Hz
0.01Hz
3Hz
10
0A
8A
0
{
{
{
{
{
{
11
DC injection brake operation time
0 to 10s
0.1s
0.5s
11
0B
8B
0
{
{
{
{
{
{
12
DC injection brake operation voltage
0 to 30%
0.1%
6/4/2%
12
0C
8C
0
{
{
{
{
{
{
-
13
Starting frequency
0 to 60Hz
0.01Hz
0.5Hz
13
0D
8D
0
{
{
{
{
{
{
-
14
Load pattern selection
0 to 3
1
0
14
0E
8E
0
{
×
×
{
{
{
JO
G
oper
at
ion
15
Jog frequency
0 to 400Hz
0.01Hz
5Hz
15
0F
8F
0
{
{
{
{
{
{
16
Jog acceleration/deceleration time
0 to 3600/360s
0.1/0.01s
0.5s
16
10
90
0
{
{
{
{
{
{
-
17
MRS input selection
0, 2, 4
1
0
17
11
91
0
{
{
{
{
{
{
-
18
High speed maximum frequency
120 to 400Hz
0.01Hz
120Hz
18
12
92
0
{
{
{
{
{
{
-
19
Base frequency voltage
0 to 1000V, 8888, 9999
0.1V
9999
19
13
93
0
{
×
×
{
{
{
A
cc
e
le
ra
tion/
dec
e
lerat
ion t
im
e
20
Acceleration/deceleration reference
frequency
1 to 400Hz
0.01Hz
60Hz
20
14
94
0
{
{
{
{
{
{
21
Acceleration/deceleration time increments 0, 1
1
0
21
15
95
0
{
{
{
{
{
{
St
a
ll
prev
ent
ion
22
Stall prevention operation level
0 to 200%
0.1%
150%
22
16
96
0
{
{
{
{
{
{
23
Stall prevention operation level
compensation factor at double speed
0 to 200%, 9999
0.1%
9999
23
17
97
0
{
{
{
{
{
{
Содержание FR-A700 Series
Страница 245: ...279 2 PARAMETER PARAMETER MEMO ...
Страница 440: ...474 PARAMETER MEMO ...
Страница 522: ...556 SELECTION MEMO ...