268
PARAMETER
2.8.2
Offline auto tuning function
[ Pr. 71, 80 to 84*, 90 to 94*, 96, 450*, 453 to 463*, 684*, 859*, 860*]
(A700)(E700)(D700)
Auto tuning function is designed to automatically measures
the motor constants necessary for Advanced magnetic flux
vector control, Real sensorless vector control, and vector
control operation.
The motor can be run with the optimum operating
characteristics even when each motor constants differs,
other manufacturer's motor is used, or the wiring length is
long.
Also, tuning data (motor constants) can be copied to
another inverter with the operation panel or FR-PU07
parameter unit.
Note that a high-slip motor, high-speed motor, or other
special motor cannot be tuned. Also, the highest speed
should be 120Hz.
What is auto tuning?
1) The motor performance can be maximized.
2) Auto tuning function is recommended for improvement of motor operation performance. (Always perform auto tuning when
using Real sensorless vector control.)
3) There are two different auto tuning: offline auto tuning (measures motor constants before machine operation) and online
auto tuning (measures motor constants at every start of the inverter).
4) Tuning without motor running and with motor running are available for offline auto tuning.
5) Accuracy of speed characteristics
Online
offline (with motor running) offline (without motor running)
without tuning
1)
A700 E700 D700
(*[
Pr. 450, 453 to 463, 684, 860
] are not available for
.)
(*[
Pr. 81, 91 to 94, 450, 453 to 463, 684, 859, 860
] are not available for
.)
F700
F700
A700
[
Pr.
]
Name
Initial
Value
Setting Range
Description
71
Applied motor
0
0 to 8, 13 to 18, 20, 23, 24, 30, 33,
34, 40, 43, 44, 50, 53, 54
By selecting a standard motor or constant torque motor, thermal
characteristic and motor constants of each motor are set.
80
Motor capacity
9999
55K or less
0.4 to 55kW
Set the applied motor capacity.
75K or more
0 to 3600kW
9999
V/F control
81
Number of motor poles
9999
2, 4, 6, 8, 10
Set the number of motor poles.
12, 14, 16, 18, 20
X18 signal-ON: V/F control
Set 10 + number of motor poles .
9999
V/F control
82
Motor excitation current 9999
55K or less
0 to 500A
Tuning data
(The value measured by offline auto tuning is automatically set.)
75K or more
0 to 3600A
9999
Uses the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA, SF-HRCA,
SF-V5RU(1500r/min series)) constants
83
Rated motor voltage
200/
400V
*
0 to 1000V
Set the rated motor voltage(V).
*The initial value differs according to the voltage class. (200V/400V)
84
Rated motor frequency
60Hz
10 to 120Hz
Set the rated motor frequency (Hz).
90
Motor constant (R1)
9999
55K or less
0 to 50
,
9999
Tuning data
(The value measured by offline auto tuning is automatically set.)
9999: Uses the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
SF-HRCA, SF-V5RU(1500r/min series)) constants
75K or more
0 to 400m , 9999
91
Motor constant (R2)
9999
55K or less
0 to 50
,
9999
75K or more
0 to 400m , 9999
92
Motor constant (L1)
9999
55K or less
0 to 50
(0 to 1000mH),
9999
75K or more
0 to 3600m (0 to 400mH),
9999
93
Motor constant (L2)
9999
55K or less
0 to 50
(0 to 1000mH),
9999
75K or more
0 to 3600m
(0 to 400mH),
9999
94
Motor constant (X)
9999
55K or less
0 to 500 (0 to 100%), 9999
75K or more 0 to 100
(0 to 100%), 9999