248
PARAMETER
2.6.2
Adjustable 5 points V/F [Pr. 71, 100 to 109]
(A700)(F700)
When V/F control has been selected, set [
Pr. 71 = 2
] and
define five points as shown on the right to perform
operation in the V/F pattern connected by straight lines in
sequence.
For a machine of large static friction coefficient and small
dynamic static friction coefficient, for example, set a V/F
pattern that will increase the voltage only in a low speed
region since such a machine requires large torque at a
start.
When [
Pr. 19 Base frequency voltage
= 8888, 9999], [
Pr. 71 =
2
] can not be set. Set the rated voltage value in [
Pr. 19
] to
set [
Pr. 71 = 2
].
The five points can be set as desired within the range of
the [
Pr. 3 Base frequency
], and [
Pr. 19 Base frequency voltage
].
Note that if you attempt to set the same frequency in any
two of the five points, an outside-of -range error occurs.
The setting of inappropriate V/F values will cause
excessive current, abnormal machine collision or vibration
during acceleration and deceleration.
When [
Pr. 71 = 2
] is set, [
Pr. 47 Second V/F
] and [
Pr. 113 Third
V/F
] will not function.
The electronic thermal relay function calculates as
standard motor.
Adjustable 5 points V/F does not function during Advanced
magnetic flux vector control, Simple magnetic flux vector
control, Real sensorless vector control, vector control.
A700 F700
Base frequency
voltage
[
Pr.19
]
Base frequency
[
Pr.3
]
Torque boost
[
Pr.0
]
V/F Characteristic
0
V/F5
V/F4
V/F3
V/F2
V/F1
Frequency
Voltage
[
Pr.
]
Name
Initial
Value
Setting Range
Description
71
Applied motor
0
0 to 8, 13 to 18,
20, 23, 24, 30, 33,
34, 40, 43, 44, 50,
53, 54
Set 2 for adjustable 5 points V/F control.
0, 1, 2, 20
100
V/F1 (first frequency)
9999
9999
No V/F1 setting
0 to 400Hz
Set the V/F1 frequency
101
V/F1(first frequency voltage)
0V
0 to 1000V
Set the V/F1 voltage
102
V/F2 (second frequency)
9999
9999
No V/F2 setting
0 to 400Hz
Set the V/F2 frequency
103
V/F2 (second frequency
voltage)
0V
0 to 1000V
Set the V/F2 voltage
104
V/F3 (third frequency)
9999
9999
No V/F3 setting
0 to 400Hz
Set the V/F3 frequency
105
V/F3 (third frequency
voltage)
0V
0 to 1000V
Set the V/F3 voltage
106
V/F4 (fourth frequency)
9999
9999
No V/F4 setting
0 to 400Hz
Set the V/F4 frequency
107
V/F4 (fourth frequency
voltage)
0V
0 to 1000V
Set the V/F4 voltage
108
V/F5 (fifth frequency)
9999
9999
No V/F5 setting
0 to 400Hz
Set the V/F5 frequency
109
V/F5 (fifth frequency voltage)
0V
0 to 1000V
Set the V/F5 voltage
A700
F700
Содержание FR-A700 Series
Страница 245: ...279 2 PARAMETER PARAMETER MEMO ...
Страница 440: ...474 PARAMETER MEMO ...
Страница 522: ...556 SELECTION MEMO ...