PARAMETER
<Set point input calibration>
<Detector output calibration>
The results of the above calibration are as shown below:
1) Apply the input voltage of 0% set point setting (e.g.
0V) across terminals 2-5.
2) Enter in [
C2 (Pr. 902)
] the frequency which should be
output by the inverter at the deviation of 0% (e.g.
0Hz).
3) In [
C3 (Pr. 902
)], set the voltage value at 0%.
4) Apply the voltage of 100% set point (e.g. 5V) across
terminals 2-5.
5) Enter in [
Pr. 125
] the frequency which should be
output by the inverter at the deviation of 100% (e.g.
60Hz).
6) In [
C4 (Pr. 903)
], set the voltage value at 100%.
1) Apply the output current of 0% detector setting (e.g.
4mA) across terminals 4-5.
2) Make calibration using [
C6 (Pr. 904)
].
3) Apply the output current of 100% detector setting
(e.g. 20mA) across terminals 4-5.
4) Make calibration using [
C7 (Pr. 905)
] .
5) The frequency set in [
C5 (Pr. 904)
] and [
Pr. 126
]
should be the same as set in [
C2 (Pr. 902)
] and [
Pr.
125
].
100
0
0
5
(V)
(%)
[Set point setting]
0
0
20
(mA)
[Detection value]
4
100
(%)
60
0
0
100 Deviation(%)
[Manipulated value]
Manipulated
value(Hz)