253
2
P
ARAM
ETE
R
PARAMETER
(1) Selection of control method and control
mode
1) FR-A700 series
Select the inverter control method from V/F control,
Advanced magnetic flux vector control (speed
control), Real sensorless vector control (speed
control, torque control) and vector control (speed
control, torque control, and position control).
When vector control test operation ([
Pr. 800 = 9
]) is
selected, speed control test operation can be
performed without the motor connected. The
speed calculation value changes to track the
speed command, and the transition can be
checked with the operation panel and analog
signal output at terminal FM and AM.
<First motor selection>
<Second motor selection>
[
Pr.
]
Name
Initial
Value
Setting Range
Description
80
Motor capacity
9999
55K or less
0.4 to 55kW
Set the applied motor capacity.
75K or more
0 to 3600kW
9999
V/F control
81
Number of motor poles
9999
2, 4, 6, 8, 10
Set the number of motor poles.
12, 14, 16, 18, 20
X18 signal-ON: V/F control Set 10 + number of motor poles.
9999
V/F control
450 Second applied motor
9999
0 to 8, 13 to 18, 20, 23, 24, 30,
33, 34, 40, 43, 44, 50, 53, 54
Set when using the second motor.
(Same specifications as [
Pr. 117
] )
9999
Function invalid ([
Pr. 71
] is valid.)
451
Second motor control
method selection
9999
10, 11, 12
Real sensorless vector control
20, 9999
V/F control (Advanced magnetic flux vector control)
453 Second motor capacity
9999
55K or less
0.4 to 55kW
Set the capacity of the second motor.
75K or more
0 to 3600kW
9999
V/F control
454
Number of second
motor poles
9999
2, 4, 6, 8, 10
Set the number of poles of the second motor.
9999
V/F control
800
Control method
selection
20
0 to 5
V/F control *
Vector control
9
Vector control test operation
10, 11, 12
Real sensorless vector control
20
Advanced magnetic flux vector control
* When [
Pr.80 Motor capacity = 9999
] or [
Pr.81 Number of motor poles = 9999
], control method is V/F control regardless of [
Pr.800
] setting.
[
Pr. 80, 81
]
[
Pr. 800
] Setting
Control Method
Control Mode
Remarks
Other than 9999
0
Vector control
Speed control
—
1
Torque control
—
2
Speed control/torque
control switchover
MC signal: ON Torque control
MC signal: OFF Speed control
3
Position control
—
4
Speed control/position
control switchover
MC signal: ON Position control
MC signal: OFF Speed control
5
Position control/torque
control switchover
MC signal: ON Torque control
MC signal : OFF Position control
9
Vector control test operation
10
Real sensorless vector control
Speed control
—
11
Torque control
—
12
Speed control/torque
control switchover
MC signal: ON Torque control
MC signal: OFF Speed control
20
([
Pr. 800
] initial value)
Advanced magnetic flux
vector control
Speed control
—
9999
—
*
V/F control
* Control method is V/F control regardless of the setting value of [
Pr. 800
] when [
Pr. 80 Motor capacity
= 9999] or [
Pr. 81 Number of motor
poles =
9999].
Setting [
Pr. 450
≠
9999] selects the second motor control.
[
Pr. 450
]
[
Pr. 453, Pr. 454
]
[
Pr. 451
] Setting
Control Method
Control Mode
Remarks
Other than
9999
Other than 9999
10
Real sensorless vector
control
Speed control
—
11
Torque control
—
12
Speed control/torque
control switchover
MC signal: ON Torque control
MC signal: OFF Speed control
20
Advanced magnetic
flux vector control
Speed control
—
9999
([
Pr. 451
] initial value)
Advanced magnetic
flux vector control
Speed control
—
9999
—
*
V/F control
9999
—
—
Second motor function is invalid
* Control method is V/F control regardless of the setting value of [
Pr. 451
] when [
Pr. 453 Second motor capacity = 9999
] or [
Pr. 454 Number of
motor poles = 9999
].
Содержание FR-A700 Series
Страница 245: ...279 2 PARAMETER PARAMETER MEMO ...
Страница 440: ...474 PARAMETER MEMO ...
Страница 522: ...556 SELECTION MEMO ...