454
PARAMETER
[Example] When reading the [
C3 (Pr. 902)
] and [
C6 (Pr. 904)
] settings from the inverter of station 0
List of calibration parameters
12
Second parameter
changing
(instruction code
HFF = 1, 9)
Read
H6C
Setting calibration parameter
*5
H00: Frequency
*6
H01: Parameter-set analog value
H02: Analog value input from terminal
*5
Refer to the list of calibration parameters below for
calibration parameters.
*6
The gain frequency can be written using [
P. 125
] (instruction
code H99) or [
Pr. 126
] (instruction code H9A) also.
2 digits
(B
,
E1/D)
Write
HEC
*
3
2 digits
(A1
,
C/D)
13
*4
Multi command
Write/
Read
HF0
Available for writing 2 commands, and monitoring 2 items for
reading data (
Refer to page 458
for detail)
10 digits
(A3, C1/D)
14
*4
In
ve
rt
e
r ty
p
e
m
o
n
ito
r
Inverter
type
Read
H7C
Reading inverter type in ASCII code.
"H20" (blank code) is set for blank area
Example of FR-D740
H46, H52, H2D, H44, H37, H34, H30, H20.. H20
20 digits
(B, E3/D)
Capacity
Read
H7D
Reading inverter capacity in ASCII code.
Data is read in increments of 0.1kW, and rounds down to 0.01kW
increments
"H20" (blank code) is set for blank area
Example
0.4K................. " 4" (H20, H20, H20, H20, H20, H34)
0.75K............... " 7" (H20, H20, H20, H20, H20, H37)
6 digits
(B, E2/D)
*1
for data format.
*2
Set 65520 (HFFF0) as a parameter value 8888 and 65535 (HFFFF) as 9999.
*3
For the instruction codes HFF, HEC and HF3, their values are held once written but cleared to zero when an inverter reset or
all clear is performed.
*4
Setting is available for only
.
Computer Send Data
Inverter Send Data
Description
1)
ENQ 00 FF 0 01 82
ACK 00
Set H01 to the expansion link parameter.
2)
ENQ 00 EC 0 01 7E
ACK 00
Set H01 to second parameter changing.
3)
ENQ 00 5E 0 0F
STX 00 0000 ETX 25
[
C3(Pr. 902)
] is read. 0% is read.
4)
ENQ 00 60 0 FB
STX 00 0000 ETX 25
[
C6(Pr. 904)
] is read. 0% is read.
To read/write [
C3 (Pr. 902)
] and [
C6 (Pr. 904)
] after inverter reset or parameter clear, execute from 1) again.
No.
Item
Read/
Write
Instruction
Code
Data Description
Number of
Data Digits
*
1
(format)
D700
[Pr.]
Name
Instruction Code
Read Write Expansion
C2 (902)
Terminal 2 frequency setting bias
frequency
5E
DE
1
C3 (902) Terminal 2 frequency setting bias
5E
DE
1
125 (903)
Terminal 2 frequency setting gain
frequency
5F
DF
1
C4 (903) Terminal 2 frequency setting gain
5F
DF
1
C5 (904)
Terminal 4 frequency setting bias
frequency
60
E0
1
C6 (904) Terminal 4 frequency setting bias
60
E0
1
126 (905)
Terminal 4 frequency setting gain
frequency
61
E1
1
C7 (905) Terminal 4 frequency setting gain
61
E1
1
C12 (917)
Terminal 1 bias frequency (speed)
11
91
9
C13(917)
*1
Terminal 1 bias (speed)
11
91
9
*1
These are not available for
.
*2
These are not available for
.
F700
E700
D700
A700
F700
[Pr.]
Name
Instruction Code
Read Write Expansion
C14 (918)
*1
Terminal 1 gain frequency (speed)
12
92
9
C15 (918)
*1
Terminal 1 gain (speed)
12
92
9
C16 (919)
*1
Terminal 1 bias command
(torque/magnetic flux)
13
93
9
C17 (919)
*1
Terminal 1 bias (torque/magnetic flux)
13
93
9
C18 (920)
*1
Terminal 1 gain command (torque/
magnetic flux)
14
94
9
C19 (920
) *1
Terminal 1 gain (torque/magnetic flux)
14
94
9
C22 (922
) *2
Frequency setting voltage bias
frequency (built-in potentiometer)
16
96
9
C23 (922
) *2
Frequency setting voltage bias (built-in
potentiometer)
16
96
9
C24 (923
) *2
Frequency setting voltage gain
frequency (built-in potentiometer)
17
97
9
C25 (923
) *2
Frequency setting voltage gain (built-in
potentiometer)
17
97
9
C38 (932)
*1
Terminal 4 bias command (torque/
magnetic flux)
20
A0
9
C39 (932)
*1
Terminal 4 bias (torque/magnetic flux)
20
A0
9
C40 (933)
*1
Terminal 4 gain command (torque/
magnetic flux)
21
A1
9
C41 (933)
*1
Terminal 4 gain (torque/magnetic flux)
21
A1
9