270
PARAMETER
2)
3)
E700
[
Pr.
]
Name
Initial Value
Setting Range
Description
71 Applied motor
0
0, 1, 3 to 6, 13 to 16, 23,
24, 40, 43, 44, 50, 53,
54
By selecting a standard motor or constant torque motor, thermal
characteristic and motor constants of each motor are set.
80 Motor capacity
9999
0.1 to 15kW
Applied motor capacity.
9999
V/F control
81 Number of motor poles
9999
2, 4, 6, 8, 10
Number of motor poles.
9999
V/F control
82 Motor excitation current
9999
0 to 500A
Tuning data
(The value measured by offline auto tuning is automatically set.)
9999
Uses the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA, SF-
HRCA) constants
83 Rated motor voltage
200V class 200V
0 to 1000V
Rated motor voltage(V).
400V class 400V
84 Rated motor frequency
60Hz
10 to 120Hz
Rated motor frequency (Hz).
90 Motor constant (R1)
9999
0 to 50
Ω
,
9999
Tuning data
(The value measured by offline auto tuning is automatically set.)
9999: Uses the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
SF-HRCA) constants
91 Motor constant (R2)
9999
0 to 50
Ω
,
9999
92 Motor constant (L1)
9999
0 to 1000mH, 9999
93 Motor constant (L2)
9999
0 to 1000mH, 9999
94 Motor constant (X)
9999
0 to 100%, 9999
96
Auto tuning setting/
status
0
0
Offline auto tuning is not performed
1
For Advanced magnetic flux vector control
Offline auto tuning is performed without motor running (all motor
constants).
11
For General-purpose magnetic flux vector control
Offline auto tuning is performed without motor running.
(motor constant (R1) only)
21
Offline auto tuning for V/F control
(automatic restart after instantaneous power failure (with
frequency search))(Refer to page 367)
859 Torque current
9999
0 to 500A
Tuning data
(The value measured by offline auto tuning is automatically set.)
9999
Uses the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA, SF-
HRCA) constants
D700
[
Pr.
]
Name
Initial Value
Setting Range
Description
71
Applied motor
0
0, 1, 3, 13, 23, 40, 43,
50, 53
By selecting a standard motor or constant torque motor,
thermal characteristic and motor constants of each motor are
set.
80
Motor capacity
9999
0.1 to 7.5kW
Applied motor capacity.
9999
V/F control
82
Motor excitation current
9999
0 to 500A
Set motor excitation current (no load current)
9999
Uses the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA, SF-
HRCA) constants
83
Rated motor voltage
400V
0 to 1000V
Rated motor voltage(V).
84
Rated motor frequency
60Hz
10 to 120Hz
Rated motor frequency (Hz).
90
Motor constant (R1)
9999
0 to 50
Ω
,
9999
Tuning data
(The value measured by offline auto tuning is automatically
set.)
9999: Uses the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
SF-HRCA) constants
96
Auto tuning setting/
status
0
0
Offline auto tuning is not performed
11
For General-purpose magnetic flux vector control
Offline auto tuning is performed without motor running.
(motor constant (R1) only)
21
Offline auto tuning for V/F control (automatic restart after
instantaneous power failure (with frequency search))
(Refer to page 367)