275
2
P
ARAM
ETE
R
PARAMETER
3) Refer to the following table and set [
Pr. 83 and Pr.
84
].
To enter the [
Pr. 92, 93
] motor constants in [mH]
<Operating procedure>
1) Set the following value in [
Pr. 71
]
2) In the parameter setting mode, read the following
parameters and set desired values. Mitsubishi
motor constants are used when 9999 is set in [
Pr.
82, 90 to 94, 859
].
Calculate the [
Pr. 94
] value from the following
formula.
[
Pr. 94
] Setting = (1-
) 100(%)
3) Refer to the following table and set [
Pr. 83, 84
].
(6) Perform tuning of the second applied
motor
When you want to switch between two motors with
one inverter, set the second motor in [
Pr. 450 Second
applied motor
] (refer to page 266). Initial setting is
without second applied motor.
Turning the RT signal ON makes the following
parameters for the second motor valid.
To perform auto tuning of the second motor, replace
the parameter number stated in the previous
explanation with the parameter number
corresponding to the one for the second motor in the
table below.
[
Pr.
]
Name
Setting
Range
Setting
Range
83
Rated motor voltage
0 to 1000V
0.1V
84
Rated motor frequency 10 to 120Hz
0.01Hz
Motor
[
Pr. 71
]
Setting
Mitsubishi standard
motor
Mitsubishi high
efficiency motor
SF-JR
0
SF-JR 4P 1.5kW or less
20*
SF-HR
40
Mitsubishi constant-
torque motor
SF-JRCA 4P
1
SF-HRCA
50
Vector control
dedicated motor
SF-V5RU (1500r/min
series)
30*
* Available only for
.
[
Pr.
]
Name
Setting Range
(
Upper line : 55K or less
Lower line : 75K or more
)
Setting
Increments
82
Motor excitation
current (no load
current)
0 to 500A
,
9999
0.01A
0 to 3600A
,
9999
0.1A
90
Motor constant
(r1)
0 to 50
Ω
,
9999
0.001
Ω
0 to 400m
Ω
, 9999
0.01m
Ω
91
Motor constant
(r2)
0 to 50
Ω
, 9999
0.001
Ω
0 to 400m
Ω
, 9999
0.01m
Ω
92
Motor constant
(x1)
0 to 50
Ω
,
9999
0.001
Ω
0 to 3600m
Ω
, 9999
0.01m
Ω
93
Motor constant
(x2)
0 to 50
Ω
,
9999
0.001
Ω
0 to 3600m
Ω
, 9999
0.01m
Ω
94
Motor constant
(xm)
0 to 500
Ω
,
9999
0.01
Ω
0 to 100
Ω
, 9999
859
Torque current
0 to 500A
,
9999
0.01A
0 to 3600A
,
9999
0.1A
A700
M
2
L1
L2
L1= I1+ M: Primary inductance
L2= I2+ M: Secondary inductance
M
V
R2/S
R1
I1
I2
R1: Primary resistance
I1: Primary leakage inductance
I2: Secondary leakage inductance
M: Excitation inductance
S: Slip
R2: Secondary resistance
Motor equivalent circuit diagram
[
Pr.
]
Name
Setting
Range
Setting
Range
83
Rated motor voltage
0 to 1000V
0.1V
84
Rated motor frequency 10 to 120Hz
0.01Hz
Functions
RT Signal is ON
Second Motor
RT Signal is
OFF
First Motor
Motor capacity
[
Pr. 453
]
[
Pr. 80
]
Number of motor
poles
[
Pr. 454
]
[
Pr. 81
]
Motor excitation
current
[
Pr. 455
]
[
Pr. 82
]
Rated motor voltage
[
Pr. 456
]
[
Pr. 83
]
Rated motor
frequency
[
Pr. 457
]
[
Pr. 84
]
Motor constant (R1)
[
Pr. 458
]
[
Pr. 90
]
Motor constant (R2)
[
Pr. 459
]
[
Pr. 91
]
Motor constant (L1)
[
Pr. 460
]
[
Pr. 92
]
Motor constant (L2)
[
Pr. 461
]
[
Pr. 93
]
Motor constant (X)
[
Pr. 462
]
[
Pr. 94
]
Auto tuning setting/
status
[
Pr. 463
]
[
Pr. 96
]
[
Pr.
]
Name
Setting Range
(
Upper line : 55K or less
Lower line : 75K or more)
Setting
Increments
82
Motor excitation
current (no load
current)
0 to 500A, 9999
0.01A
0 to 3600A, 9999
0.1A
90
Motor constant (R1)
0 to 50
Ω
,
9999
0.001
Ω
0 to 400m
Ω
, 9999
0.01m
Ω
91
Motor constant (R2)
0 to 50
Ω
,
9999
0.001
Ω
0 to 400m
Ω
, 9999
0.01m
Ω
92
Motor constant (L1)
0 to 1000mH, 9999
0.1mH
0 to 400mH, 9999
0.01mH
93
Motor constant (L2)
0 to 1000mH, 9999
0.1mH
0 to 400mH, 9999
0.01mH
94
Motor constant (X)
0 to 100%, 9999
0.1%
0 to 100%, 9999
0.01%
859
Torque current
0 to 500A, 9999
0.01A
0 to 3600A, 9999
0.1A
A700