(3) PU/External combined operation mode 1
[
Pr. 79 = 3
]
Select the PU/External combined operation mode 1
when inputting the frequency command from the
operation panel (FR-DU07/FR-PA07) or parameter
unit (FR-PU04/FR-PU07) and inputting the start
command with the external start switch.
Select [
Pr. 79 = 3
] . You cannot change to the other
operation mode.
When a frequency is input from the external signal
by multi-speed setting, it has a higher priority than
the frequency command from the PU. When AU
signal is ON, command signal is given to terminal 4.
(4) PU/External combined operation mode 2
[
Pr. 79 = 4
]
Select the PU/External combined operation mode 2
when inputting the frequency command from the
external potentiometer, multi-speed or JOG signal
and inputting the start command by key operation of
the operation panel (FR-DU07/FR-PA07) or
parameter unit (FR-PU04/FR-PU07).
Select [
Pr. 79 = 4
] . You cannot change to the other
operation mode.
Three-phase
AC power supply
Motor
Inverter
R/L1
S/L2
T/L3
U
V
W
FR-DU07
STR
Forward rotation
start
Reverse rotation
start
STF
SD
Three-phase
AC power supply
Motor
Frequency setting
potentiometer
Inverter
R/L1
S/L2
T/L3
U
V
W
5
10
2
FR-DU07
,
3
4
5 6
7
8
9
10
Hz