102
SPECIFICATIONS
(2) Alarms
Opposite rotation
deceleration fault
The speed may not decelerate during low
speed operation if the rotation direction of
the speed command and the estimated
speed differ when the rotation is changing
from forward to reverse or from reverse to
forward under torque control of Real
sensorless vector control. At this time, the
inverter output is stopped if the rotation
direction will not change, causing overload.
(E.11)
Fault 11
{
—
—
—
Internal circuit fault
Appears when an internal circuit fault
occurred.
(E.13)
Fault 13
{
{
{
—
Safety circuit fault
Appears when safety circuit is
malfunctioning, or when one of the lines
between S1 and SC, or between S2 and SC
is opened.
(E.SAF)
Fault 14
Fault
E.SAF
—
—
—
{
Name
Description
Indication
Available Inverters
Operation
panel
Parameter unit
FR-PU04 FR-PU07
A700
F700
E700
D700
common
Name
Description
Indication
Available Inverters
Operation
panel
Parameter unit
FR-PU04 FR-PU07
Fan alarm
For the inverter that contains a cooling fan,
appears on the operation panel when the cooling
fan stops due to a fault or different operation from
the setting of [
Pr. 244 Cooling fan operation selection
].
(FN)
FN
{
{
{
{
A700
F700
E700
D700