8. Maintenance Functions
8.2 Data Sampling
III
-67
(3) #0 SMT START (setting range: 0, 1, 9)
0: Sampling
stop
1: Sampling
start
9:
Sampling forced end
Sampling will start when "1" is set. This will be set to "0" when sampling is completed.
The operation when "1" is set will differ according to the #5 setting.
#5 setting
Operation
0 Sampling
starts
immediately.
Other than 0
System waits for trigger, and sampling starts when trigger is
detected.
If "9" is set during the sampling process, the sampling will stop immediately, and the value will be set
to 0.
(4) #1 CYCLE (setting range: 1 to 255)
Set the sampling cycle.
Cycle = 1.7ms
∗
2
∗
scale
Scale = (setting value + 1) /2 [integer value]
(Example)
When setting value is 1 or 2: 3.5ms cycle
When setting value is 3 or 4: 7.1ms cycle
(5) #2 MARKS (setting range: 1 to 8)
Set the number of sampling points.
(Note)
The sampling buffer will be divided by the set number of points. The number of samples per
point will decrease when the number of sampling points is increased.
(6) #3 BUFFER (setting range: 0 to 1)
Set the range of the buffer to be used.
0:
Internal memory (DRAM)
1:
Memory cassette (capacity is automatically judged) ….. Not usable
(7) #4 CAPACITY (setting range: 0 to 2)
Set the capacity of the buffer used for sampling.
Buffer capacity = (setting value + 1)
∗
1024 items