B. Specifications
Control Panels
• Major alarm:
A failure of any circuit board.
Failure of both power supplies.
The internal panel temperature is greater than 60°C.
(FFCP, CFCP) A detected failure of an attached transition lever arm.
(SCP) The panel has been in one of the following states for greater than 5 minutes:
a Panel restarting or panel startup.
b Panel shutdown.
c Panel restarting.
d Internal panel communication problem.
• Minor alarm:
Failure of one power supply.
Fan failure or over temperature (> 50°C).
The alarm outputs are SPDT relay terminals (NC, NO, COM) as are the GPI output terminals.
External GPI and alarm circuits are determined by the customer.
S
An alarm will clear when all of the triggering conditions are off for 5–10 seconds continuously.
Power applied to the GPI inputs can be from 5 to 24 VDC, and less than 30mA. Typically, 5V at
1mA. Loads for the GPI and alarm outputs can be larger:
Max current:
1A
Max voltage:
125VAC, 110 VDC.
Max capacity:
62.5 VA, 33W.
Rated loads:
1A at 30 VDC; 0.3A at 110VDC; 0.5A at 125VAC.
Содержание NV5100MC Master Control
Страница 14: ...xiv Rev 2 10 17 Feb 11 Table of Contents ...
Страница 54: ...40 Rev 2 10 17 Feb 11 3 Frames Other Modules ...
Страница 92: ...78 Rev 2 10 17 Feb 11 4 MCPMs Other General Features ...
Страница 112: ...98 Rev 2 10 17 Feb 11 5 MCEs Summary ...
Страница 158: ...144 Rev 2 10 17 Feb 11 6 Control Panels Aux Preview GUI ...
Страница 166: ...152 Rev 2 10 17 Feb 11 7 Other MC Products Device Controller ...
Страница 224: ...210 Rev 2 10 17 Feb 11 C Misc Information NorthAmerican andInternational PowerCords ...
Страница 240: ...226 Rev 2 10 17 Feb 11 Index ...