2. To disable internal selective high voltage shutdown
(ISHVSD), open S3.5 on the CM2 board for 48V
rectifiers. For 24V applications, open S3.6 to disable
ISHVSD. See Figure 6-3.
3. To raise the backup HVSD level, adjust S3.1-S3.4 on CM2
to one of the levels given in Table A on the rectifier door.
Choose a level 1 to 2 volts above the initial charge voltage.
4. Close the rectifier door and turn the Power switch On. The
green Power LED must be on. (If not, do not attempt to
turn on the circuit breaker, CB1. Troubleshoot the problem
per Section 7). Keep the rectifier on for 10 seconds.
5. Hold the meter selector switch in the Rect V position, and
use a small screwdriver to turn the Float Adj
potentiometer clockwise until the digital meter reads
approximately battery voltage, typically 52 volts.
6. Turn circuit breaker CB1 on (up).
7. Adjust the Float Adj potentiometer to obtain the desired
initial charge voltage within the limits specified by the
battery manufacturer.
After completing the initial charge,
1. Turn the rectifier Power switch Off and the circuit breaker
off (down).
2. Restore the original switch settings by closing S3.5 (48V)
or S3.6 (24V) and restoring the backup HVSD on the CM2
board. Refer to switch setting label located on the inside of
the rectifier door.
3. To restore the rectifier to service, follow the procedure in
Section 7.
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...