Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
Issue 8 January 1999
Troubleshooting and Adjustments 7 - 15
Adjust Current
Limit
Off Line Adjustment: Use the Current Limit Test (Off Line) to
verify that the current limit circuit needs adjustment, before
continuing with this procedure.
Amps
± 2.5% of reading ± 2 amperes*
*
To compare, measure the shunt voltage. 1mV of shunt voltage indicates
5 amperes of output current. For example, the shunt voltage should be
40 mV at full load (200 amperes). At 125% of full load (250 amperes),
the shunt voltage should be 50 mV.
Table 7-G: Digital Meter Tolerance
Switch Position
Tolerance
Figure 7-1: Adjustment Potentiometer on CM3
Digital Meter Potentiometer
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...