Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
Issue 8 January 1999
Replacing Components and Circuit Modules 8 - 7
1. DC Capacitors C5 through C9 are located behind the
capacitor bus bars. The bus bars are mounted directly to
the capacitors by the capacitor terminal screws. In order to
remove a capacitor, remove fuse board CM1, the capacitor
terminal screws, mounting screws, and the screw
supporting the fuse assembly. Note that this completely
frees the capacitor bus bar in question.
2. Remove the capacitor from its clamp by pulling toward
you on the capacitor.
3. Replace the capacitor by pushing it into the clamp with the
positive terminal toward the inside.
Note
All output capacitors should be replaced if any are being
replaced.
4. Replace the negative bus bar. Tighten the mounting screws
first and then the capacitor terminal screws.
5. Replace the fuse assembly. Replace fuse if required.
CB1 Circuit
Breaker
1. Remove the output cables to the rectifier.
2. Remove the bolts securing the input bus bar to the circuit
breaker.
3. Support the breaker and remove the four screws securing
the breaker to the side upright. Note that there are two
alarm connections attached to the rear of the breaker.
Remove these once the breaker is free.
4. Reinstall in reverse order.
DC Inductor
(L3, L4)
Note
Before replacing a dc inductor (L3 or L4), remove the circuit
breaker.
1. Remove the electrical connection of the inductor to be
replaced.
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...