6 - 26 Testing
Issue 8 January 1999
load rating of the largest rectifier. You may fine tune the
output of each rectifier to reduce the overall variation in
load current. (Raise or lower the voltage in order to raise or
lower the output current with respect to other rectifiers in
the plant.) If plant voltage is not at the desired level, use
the same method to fine tune output voltage and currents at
the same time.
Note
At least two load-sharing rectifiers are required for testing. Each
rectifier must be adjusted according to Steps 1 through 9 above.
S2.7 on CM4 must be closed.
10. Verify that load-sharing rectifiers are producing the same
current ± 5% of the full load rating of the largest rectifier.
If not, fine tune according to Step 9.
11. With the rectifier load sharing, turn the Float Adj
potentiometer clockwise a few turns. The LCA LED
should light and generate an alarm on TB3-5 and TB3-6 of
CM4.
12. Restore the rectifier to load sharing according to Step 9.