Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
Issue 8 January 1999
Troubleshooting and Adjustments 7 - 1
7
Troubleshooting and
Adjustments
General
This section provides troubleshooting information and
adjustment procedures for the J85503B-2 rectifier. Whenever
working on or near electrically live equipment, observe all safety
precautions given in Section 4, Safety, and within each
procedure. For tools and test equipment required for certain
adjustments, refer to Section 5, Installation.
Disconnecting
a Rectifier
DANGER
AC voltages up to 600 volts to ground, and dc voltages of -48
volts with high current capacities, may be present in the
equipment. Follow the procedures in the order given to
minimize dangerous encounters with these voltages.
Exercise extreme caution when working near the battery bus
bars.
1. At the rectifier control panel, turn the Power switch Off.
Turn the CB1 circuit breaker Off (down).
2. At the ac service panel, remove the fuses or open the
circuit breakers which supply the rectifier with ac power.
Tag fuse holders or circuit breaker to instruct all to leave
circuit de-energized.
3. Remove regulation fuses associated with the rectifier
remote sense leads (usually located in the plant controller).
4. When a Lucent controller is used, disconnect the plant
cable assembly from the rectifier CM4 interface board at
connector P5A. The cable assembly must be removed from
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...