Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
Issue 8 January 1999
Testing 6 - 13
5. Compare the amperes calculated in Step 4 with the digital
display of the meter while the switch is in the AMPS
position.
6. If the digital display is between ±2% ±2A than the amperes
calculated in Step 4, this procedure is completed.
7. If the rectifier drain indication is not as indicated in Step 6,
calibrate the CM3 card via its R15 potentiometer as
specified in Section 7.
Off Line Test
Completion
1. Reduce the load to zero.
2. Turn the Power switch Off.
3. Turn off the ac power at the ac service panel.
4. Disconnect and remove the Battery Plant Simulator Test
Set, the DMM (Digital Multimeter), and the test load.
5. If the reason for performing the rectifier tests was to affirm
the operation of the rectifier, and was not part of total plant
testing, restore the rectifier to service by following the
procedures in Section 7. If this is part of total plant testing,
leave the plant control cable disconnected at this time, until
directed to reconnect it as part of another plant procedure.
Bringing a
Rectifier On
Line
The following steps bring the rectifier into service in preparation
for testing on line. The term “on-line” means a battery string
and/or office load is connected to the rectifier.
Perform all the preliminary checks on the plant before testing the
rectifiers. The same precautions for personal safety and
equipment protection should be taken as when testing off-line.
1. Verify the ac supply and rectifier controls are as shown in
Table 6-C.
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...