Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
Issue 8 January 1999
Installation 5 - 13
have sixteen 24-pin connectors labeled Rect 1 through
Rect 16.
For ECS controllers, open the front panel and thread the
control cable through the slot on the right side of the
controller. On the backplane of the lower shelf inside the
controller, the ECS-6U has six 40-pin connectors labeled
Rect 1 through Rect 6. The ECS-12U has twelve 40-pin
connectors labeled Rect 1 through Rect 12
Warning:
Remove the REG fuse associated with the rectifier from the
controller.
6. Plug the cable into the connector assigned to the rectifier
number determined in Step (3) above. This action will
cause a minor alarm in an MCS controller. Therefore,
notify alarm personnel that the unit is being installed.
7. If the rectifier is connected to a Lucent controller, verify
that the rectifier S2.1 switch on the 330C interface board,
CM4, is in the disable position. An MCS controller must
have version 4 software to enable an equalize feature. If
the MCS has version 4 software, cut strap ST1 on circuit
module CP2 in the controller. This allows the equalize
feature to operate correctly without causing the rectifier to
shut down. The ECS-6U controller automatically enables
equalize, and the CCS controller does not have a provision
for equalize.
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...