Dimensional Information
HX-P420 Series Installation Guide
Wiring and Circuit Diagram
Alternate Wire Rope Exit
E1
E2
E3
NOTE
Mount with Ø.25 or M6
Socket Head Cap Screws.
Alternate Wire Rope Exit
NOTE
Mount with Ø.50 or M12 Socket Head Cap Screws.
RANGE “A” “B” “C”
2”, 10” 1.12 (28.4) 1.79 (45.5) 1.21 (30.7)
3”, 15”, 30” .96(24.4) 1.95 (49.5) 1.37 (34.8)
4”, 20”, 40” .80 (20.3) 2.11 (53.6) 1.53 (38.9)
5”, 25”, 50” .64 (16.3) 2.27 (57.7) 1.69 (42.9)
60” .49 (12.4) 2.42 (61.5) 1.84 (46.7)
80” .25 (6.4) 2.66 (67.6) 2.08 (52.8)
Alternate Wire Rope Exit
Note: Di men sions in
brackets are mil li me ters.
Ex ci ta tion Volt age ..
9 to 35 VDC
Total Loop resistance Per Graph
shielded cable between the transducer and the electrical inter-
face. The shield of the cable should be open at the transducer
and ground ed at the electrical interface.
With small blade type screwdriver (.105" max. blade width X
.023" max. blade thickness), ad just the
Zero
and
Span
con-
trols on the trans duc er to set the 4 and 20 mA output limits.
Note:
The
Zero
and
Span
con trols are some what in ter ac tive
and may re quire several it er a tions to ob tain the de sired zero
and maxi-
Model HX-P420
The 4 to 20 mA output transducer is a 2-wire, loop pow ered
de vice. The transducer, pow er supply, and cur rent monitor
must be con nect ed in series as illustrated above.
The minimum supply voltage is a function of total loop resis-
tance. It may be calculated us ing the formula:
V(Min.)= (0.02 x Load Res.) + 9 VDC
It may also be determined from the ac com pa ny ing graph,
shown at right.
When mounting, insure that the baseplate of the transducer
is grounded to earth ground. For best noise immunity, use
twisted pair
mum settings. Ex tend the trans duc er's cable (on an gu lar posi-
tion transducers, ro tate shaft) to the desired zero po si tion (must
be with in 0% to 30% of range). Adjust the
Zero
con trol so that
the output cur rent is 4 mA. Then extend the ca ble (on angular
position trans duc ers, ro tate shaft) to the de sired max i mum posi-
tion (must be within 80% to 100% of range). Ad just the
Span
con trol for max i mum out put cur rent of 20 mA. Re check the zero
set ting and adjust if nec es sary. Re check the Span setting and
readjust if nec es sary.
Via Paolo Uccello 4 - 20148 Milano
Tel +39 02 48 009 757 Fax +39 02 48 002 070 [email protected] www.dspmindustria.it