7 - 10 Troubleshooting and Adjustments
Issue 8 January 1999
Table 7-E: Signals on TB3 of CM4
Alarm Status
TB3 Interface Condition
No test
RFAT
Open
RFA alarm generated without
turning the rectifier off
RFAT
Closed
No alarm
ACF, ACFR
Open
AC has failed
ACF, ACFR
Closed
No alarm
LCA, LCAR
Open
*Load share enable; output current
less than 3 amperes
LCA, LCAR
Closed
No alarm
LSF, LSFR
Open
*Load share enabled; rectifier not
load sharing
LSF, LSFR
Closed
No connection
LS Standard Load Share not
connected
Connection
LS Standard Load Share
connected (Must also be
enabled via S1.9 on CM2)
No connection
NLS Special Application
Load Share not connected
Connection
NLS Special Application
Load Share not connected
(Must also be enabled via
S2.7 on CM4)
* Load sharing applies only to the -48V rectifier.