Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
6 - 6 Testing
Issue 8 January 1999
• With the BAT fuse installed in the plant controller,
check for battery voltage between pin 5 of J5A and
ground.
• If the plant is equipped with an MCS Controller or with
a Galaxy Controller with Intelligent features, again on
J5A, check for 15-20 volts dc between pins 35 and 31.
Pin 35 should be positive with respect to pin 31.
4. Place the Battery Plant Simulator Test Set (Figure 6-1), at
a convenient location near the rectifier. Connect J5A, on
the other end of the cable from the test set, to connector
P5A on the CM4 interface board mounted on the inside of
the rectifier door. Connect the red, black, blue, and white
test clips from the test set as detailed in Table 6-A. Refer to
Figures 6-2 and 6-3.
Figure 6-2: CM1 Fuse Board with Clip Connections (Older version of CM1 on the left)
White
Test
Clip
White
Test
Clip