Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
Issue 8 January 1999
Troubleshooting and Adjustments 7 - 17
the rectifier does not operate properly, refer to
“Diagnostics” section.
8. Turn on dip switch S3.7 on CM2, restart the rectifier, and
adjust the load to at least 10 percent, 20A.
Optional: To verify proper operation of the ISHVSD
circuit, do the following:
a. Adjust the Float Adj potentiometer to obtain 56 (29.5)
± 0.5 volts. Read voltage on control panel meter by
holding meter switch in the Rect V position. The
rectifier should shut down.
b. Open switch contact S3.7, close switch contact S3.8,
and restart rectifier.
c. Adjust the Float Adj potentiometer to obtain 57 (30.0)
±0.5 volts. Read voltage on control panel meter by
holding meter switch in the Rect V position. The
rectifier should shut down.
d. Close switch contact S3.7, and restart rectifier.
e. Adjust the Float Adj potentiometer to obtain 58 (30.5)
±0.5 volts. Read voltage on control panel meter by
holding meter switch in the Rect V position. The
rectifier should shut down.
9. Set ISHVSD to desired level.
10. Remove ac power to the rectifier at the ac service panel,
and disconnect the test load.
11. Reconnect the rectifier to the battery.
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...