Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
Issue 8 January 1999
Testing 6 - 15
6. Turn rectifier Power switch On. It may be necessary to
readjust the Float Adj potentiometer further clockwise in
order for the rectifier output to return to plant float voltage
and assume any load now that it has changed to external
regulation mode.
Testing On Line
On- and off-line testing require different procedures, although
most tests can be performed in either situation. If you have just
tested the rectifier off line, it is not necessary to repeat the tests
on line.
When testing on-line, connect the rectifier control cable to the
rectifier and to the associated plant controller. Also, install the
rectifier’s associated regulation battery (sense) fuse in the
controller.
If no load is present, connect a test load to the rectifier (page
6-2). Disable load share by setting S1.9 on CM2 to 0.
If the rectifier fails any of the tests in this section, replace the
CM2 board and begin testing again.
Regulation
(NL/FL) Test
Notes
At least two rectifiers must be supplying some current when this
test is done, and the load requirement must be greater than 20A,
10% of the rated output for the rectifier under test.
Do not perform this test with load share enabled.
1. Observe the amperes reading on the Output meter. Hold
the Rect Test switch in the NL position. The output
amperes should decrease.
2. Observe the amperes reading on the Output meter. Hold
the Rect Test switch in the FL position. The output current
should increase.
Rectifier Failure
Alarm/Fuse
Alarm Test
Note
This procedure causes the rectifier to fail and issue alarms to the
plant controller. When the procedure is performed on line,
sufficient rectifiers must be operating to assume the load of the
rectifier being tested.
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...