Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
Issue 8 January 1999
Installation 5 - 5
used. The rectifier will accept one 350KCMIL cables at each of
the positive and negative output terminals. The output cables
must have a minimum rating of 90° C. KS24194 L2 (flex) or
KS24194 L3 (Class B) are recommended for the distribution of
dc power in the plant.
Figure 5-3: AC and DC Termination Points
Connections for Lists "–" Rectifiers (No List B)
with or without Optional Filter List 15 or 16
Connections for Lists "+" Rectifiers (List B)
with or without Optional Filter List 15 or 16
Not Equipped with List 15 or 16
Equipped with List 15 or 16
AC Input
DC Output
AC Input
3 Phase AC
3 Phase AC
AC Grd
AC Grd
V+
V+
V–
V–
Table 5-B: DC Output Options
Amps
Output Wire Gauge and Area
(circular mils)
Connectors or Lugs
Nut Provided
200
4/0 AWG
211,600 circ mils
WP91412 L-59 (Class B)
WP91412 L-27 (Flex)
3/8-16
350KCMIL
WP91412 L-61 (Class B)
WP91412 L-86 (Flex)
Use KS24194 L2 (flex) or KS24194 L3 (Class B) for dc power distribution.