Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
Issue 8 January 1999
Installation 5 - 11
4. Tape or otherwise insulate the connectors on the end of
each cable that does not terminate in the rectifier. Label
each cable.
5. Place the dc output return cable in cable rack.
6. Insert ends of return cables through top of rectifier and
terminate connector on the positive ground bus bar in the
rectifier. Torque connections to 30 Nm (240 in-lb). See
Figure 5-3.
7. One at a time, remove tape or insulation from connector at
other end of return cable and terminate on plant charge
ground bus bar.
8. Place ungrounded negative output cables in cable rack.
9. Insert ends of charge cables through top of rectifier and
terminate connectors on negative bus bar in rectifier.
Torque to 30 Nm (240 in-lb). See Figure 5-3.
Warning:
Battery plants are an energy hazard. Avoid arc or sparks.
Before making contact between connectors and bus bar in
the next step, use a DMM to verify a true open circuit
between each connector and known battery plant ground.
10. One at a time, remove tape or insulation from connector at
other end of charge cable and terminate on negative charge
bus bar.
Supplemental
Central Office
(CO) Ground
The central office (CO) ground is “daisy-chain” connected to all
rectifiers in a plant and terminates on the central office ground
bus. The ground conductor must be 2 AWG wire (66,370 cir
mils), or equivalent, for which a lug should be ordered and two
1/4-20 bolts are provided. Connect the CO ground to the nearest
connection point on top of the rectifier (see Figure 5-4). Torque
to 8 Nm (65 in-lb).
Plant Control
Cable Assembly
(Lucent
Controller)
All cables connecting Lucent controllers to this rectifier, have a
40-pin connector on the rectifier end, which terminates on
connector P5A of the CM4 interface board inside the rectifier
door. (See Figures 2-3, 5-3, and 5-6.) Table 5-D provides the
type of connector used to connect the cable to the controller.
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...