Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
2 - 8 Product Description
Issue 8 January 1999
Unbalance
Alarm Circuit
A severe unbalance developed in the rectifier triggers the
rectifier fail circuit. The rectifier shuts down and an alarm is
generated. This shutdown of the rectifier has a delay to prevent
false operation from transient disturbances, such as may occur
during initial turn-on.
Low Current
Alarm (LCA)
If the forced electronic load share feature is enabled (-48 volt
plants only) and any rectifier is providing less than 3 percent of
its rating, a low current alarm issues. The alarm issues at 0.5
percent of the rectifier rating and discontinues at 3 percent.
Front Panel
Controls And
Indicators
Figure 2-2 shows the control panel on front of the J85503B-2,
200-ampere rectifier. The following list describes the controls
and indicators on the control panel. Bold letters indicate labels
that appear on the control panel or inside the rectifier.
Output Meter
The digital Output meter displays the following:
•
The rectifier output current when the meter switch is in the
Amps position
Figure 2-2: J85503B-2 Control Panel
Output
Rect V
Amps
Plt V
Rect
Test
Adj
Float
FLT
EQ
Equal Adj
Rect
NL
FL
ALARM
PHA
Power
On
Auto
Off
Plant
FA
RFA
ACF
LCA
LSF
Note
In Figure 2-2, “Equal Adj” and “EQ” LEDs may be labeled
“Boost” and “BST,” respectively, for international customers.
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...