Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
Issue 8 January 1999
Installation 5 - 7
Table 5-C provides widths for use with 350CKMIL cable.
Do not route other cable rack(s) above or through the area above
the rectifiers or any other heat source.
Run the output conductors in pairs (positive and negative).
Distribute the conductors evenly across the rectifier output
racks. Pair the charge cables in the cable rack.
Figure 5-5 shows how to run the dc output cables from four 200
ampere rectifiers in a cable rack.
Handling
Equipment
Each J85503B-2 rectifier weighs at least 725 pounds. Therefore,
make arrangements to have the appropriate material handling
facilities and equipment to unload, uncrate, and set up the
rectifier. Proper handling is necessary to ensure personal safety
and protect the equipment. Each rectifier is shipped in a
tri-walled corrugated cardboard container secured to a wooden
shipping skid. Move the container with a forklift.
Lucent recommends that you use four lifting eyebolts to
facilitate placing the rectifier upright in the central office. The
four holes accommodate customer supplied lifting eyebolts. The
holes are 5/8-11 threaded. For safety reasons, use all four
Table 5-C: Rack Widths for 350KCMIL Cables
Rack Width
Number of 200 Ampere Rectifiers
12
8
15
10
20
14
25
18
Figure 5-5: DC Output Cables in Cable Rack
Rect 2
Rect 4
–
–
+
+
Rect 1
Rect 3
Cable Rack
–
+
–
+
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...