Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
7 - 18 Troubleshooting and Adjustments
Issue 8 January 1999
Restore
Rectifier to
Service
1. Set the ac supply and rectifier controls as shown in Table
7-H.
2. If the rectifier voltage was NOT at the desired float voltage
before it was turned off, rotate the Float Adj potentiometer
fully counterclockwise.
3. At the ac service panel, install the ac fuses or turn the ac
input circuit breaker On.
4. To bring the rectifier into service:
a. Turn the rectifier Power switch On. The green Power
LED must light. Wait 10 seconds.
b. Hold the meter selector switch in the Rect V position,
and use a small screwdriver to turn the Float Adj
potentiometer clockwise until the digital meter reads
approximately battery voltage.
c. Turn the rectifier Power switch Off and immediately
(within 5 seconds) turn circuit breaker CB1 on (up).
5. At the rectifier, connect the control cable connector J5A.
6. At the plant controller, install the REG fuse associated
with the rectifier that is being restored to service.
7. Turn the rectifier Power switch On.
8. Close the rectifier front door and secure the locking
screws.
Table 7-H: Control Settings Prior to Restoring a
Rectifier to Service
Controls
Position/Status
Associated ac circuit breaker or
fuses at the ac service
distribution panel
Off or fuses removed and
holders tagged “Out of
Service”
Rectifier Power switch
Off (down)
Rectifier CB1 circuit breaker
Off (down)
Rectifier REG fuse in the plant
controller
Removed
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...