Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
Issue 8 January 1999
Product Description 2 - 15
Notes for Table 2-B:
1. Can operate at 220 amperes output for periods shorter than
8 hours.
2. Measured at 54 volts or 27 volts under full load.
3. Measured on 800 ampere-hour battery with a 0.5-volt lead
drop.
4. At full load measured at battery.
5. For altitudes above 1524 meters, derate the temperature by
2 degrees Celsius per 305 meters.
Regulation off Battery
± 2%
AC Ripple
50 millivolts peak to peak (Note 3)
Output Noise
(On Battery)
Psophometric Noise
< 46 dBrnc
< 32 dBrnc (Note 3)
< 2 mV rms (Note 4)
Load Share Accuracy
±20 amperes
Heat Dissipation
3700 BTU/hr (1100 watts) (Note 2)
Power Factor
>0.97 at full load
Humidity Rating
10 - 95% non-condensing
Operating Altitude
Sea level to 3048 meters (Note 5)
Operating Temperature
0 - 35° C (Lists 1, 2, 3, 4, 5, 6)
0 - 50° C (Lists 1, 2, 3, 4, 5, 6 at 150A
output)
Audible Noise
<65 dBA
Earthquake rating
Zone 4 per Bellcore TR-EOP-000063
Width
330.2 mm (13 inches)
Height
1817.6 mm (71.56 inches)
Depth
393.7 mm (15.5 inches)
Table 2-B: J85503B-2 Rectifier Specifications
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...