Table 7-D: Controls on TB1/TB2 of CM4
Control Status
TB1/TB2 Interface Condition
No control
Rectifier restart initiated
Open circuit between RS, RSR
Momentary short applied to RS, RSR
No control
Rectifier shuts down
Rectifier turns On after being off
Open circuit between TR, TRR
Short applied between TR, TRR
Short removed from TR, TRR
No control
Rectifier shuts down
Rectifier off
Open short between HV, TRR
Short applied between HV, TRR
Short removed from HV, TRR
No control
Rectifier in equalize mode
Rectifier in float after being in equalize
Open circuit between EQL, EQLR
Short applied between EQL. EQLR
Short removed from EQL, EQLR
No control
48V rectifier turns on
48V rectifier shuts down after being On
Open circuit between RM48, TRR
Short applied between RM48, TRR
Short removed from RM48, TRR
No control
24V rectifier turns on
24V rectifier shuts down after being On
Open circuit between RM24, TRR
Short applied between RM24, TRR
Short removed from RM24, TRR