Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
Issue 8 January 1999
Installation 5 - 15
TB3. Note that when a Lucent controller is used, no
connections are permitted from an external alarm/control
bay to R+, R-, BAT and GND located on TB1 and TB2.
When a Lucent controller and an external monitoring
system are used with the rectifier, the user provides the
control cable assembly which links the rectifier to the
external monitoring system. All 34 signals obtained from
TB1, TB2, and TB3 are also present in a Lucent controller,
except the following:
RM48: This signal must be connected to turn the rectifier
on or off remotely and should not be confused with the TR
signal used to shut down the rectifier remotely.
RFA/CFA: This signal indicates that the rectifier's RFA
relay has operated or that ac power is lost or turned off.
This is not the same as an RFA signal.
EQL/EQLR: Shorting these signals together places the
rectifier in equalize mode. These signals can be used with
non-Lucent controllers or other monitoring systems
provided the level of the selective high voltage shutdown
(HVSD) on the controller is raised.
E25 and E26 on CM1, the 329A fuse board, provide
access to the 50mv, 250A shunt. E22-E23-E24 is an
isolated RFA transfer contact.
10. Secure the control cable on the cable rack and disconnect
terminal strips TB1, TB2, and TB3 from the CM4
interface board.
Plant Control
Cable Assembly
(External Alarm/
Control Bay)
If a non-Lucent controller is used, the external alarm/control bay
cable assembly is provided by the user. It connects to terminal
strips TB1, TB2, and TB3 of the CM4 interface board located in
the rectifier. Thirty-four signals are accessible from the TB1,
TB2, and TB3 terminal strips.
1. You may connect all the signals to the external alarm/
control bay. However, you must connect the following
signals:
R+ and R- to regulate externally at the batteries BAT and
GRD to energize the TR, HV, and EQ relays
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...