Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
Issue 8 January 1999
Troubleshooting and Adjustments 7 - 11
Table 7-F: Additional Conditions/Indications on the J85503B-2
Signal/Condition
Indication
BAT, GRD
Nominal 52 or 24 volt control battery fused at
1-1/3 amperes and ground should be applied
when a Lucent controller is not connected to
the rectifier. When a Lucent controller is not
present, BAT is a supply to energize the HV,
TR, and EQ relays. The GRD is connected to
TRR and can serve as the discharge GRD for
HV, TR, or RM.
R+, R-
Battery plant regulation voltage, fused at 1-1/3
amperes and regulation ground can be applied
when a Lucent controller is not connected to
the rectifier. In this situation, R+ and R- are
used for external regulation sensing.
Front panel digital meter always
active
Switch S2.2 on CM set to Closed (1)
Front panel digital meter active
only when rectifier is ON
Switch S2.2 on CM set to Open (0)
Local equalize switch enabled
Switch S2.1 on CM set to Closed (1)
Local equalize switch disabled
Switch S2.1 on CM set to Open (0)
Remote control (RM48, RM24)
enabled
Switch S1 on CM4 set to Auto/Remote
Local control (RM48, RM24)
Switch S1 on CM4 set to Local/Manual
Содержание Lineage 2000 J85503B-2
Страница 2: ......
Страница 4: ......
Страница 12: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 2 List of Figures Issue 8 January 1999 ...
Страница 18: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 1 4 Introduction Issue 8 January 1999 ...
Страница 72: ...Lucent Technologies Lineage 2000 200A Ferroresonant Rectifier J85503B 2 5 22 Installation Issue 8 January 1999 ...