Lucent Technologies Lineage
®
2000 200A Ferroresonant Rectifier J85503B-2
Issue 8 January 1999
Troubleshooting and Adjustments 7 - 5
8. Rectifier does not shut down
at no load but may shut down at
10% load or more.
1. Shorted or open triac.
1. Replace triacs.
2. Winding 13 or 14 of T1 or
T2 is open.
2. Check wiring asso-ciated
with windings 13 or 14 of T1 or
T2.
9. Rectifier will not start; ac is
present, digital meter is on, and
Power switch is on.
1. Input contactor coil may be
open.
1. Check coil of input contactor
K1. If it is open replace the
contactor.
10. Rectifier tries to start but
immediately gives RFA/CFA
alarm.
1. CM1 is defective.
1. Check fuses.
2. JT2 cable between CM2 and
triacs is defective.
2. Check JT2 cable.
3. CM5 or CM6 is defective.
3. Replace CM5 and/or CM6.
11. Control panel digital meter
does not light when rectifier is
on.
1. Defective wiring on CM3.
1. Check wiring on CM3.
2. CM3 is defective.
2. Check if contacts 2 and 5 of
K2 on cm7 are closed.
3. Check connectors J1B and
J3A.
4. Replace CM3.
12. Battery voltage, measured
by Plt V position on digital
meter, does not agree with
battery voltage measured
across Plant test jacks.
1. Connect a DMM to the Plant
jacks. Hold the meter switch in
the Plt V position while
adjusting R15 on CM3 until the
two meters agree within ± 0.02
volt.
13. Rectifier emits excessive
noise.
1. Defective magnetics
1. Call your RTAC
representative on
1-800-CAL-RTAC
(1-800-225-7822).
Rectifier tests OK off line, but
does not deliver current when
connected to plant.
Rectifier was on internal
sensing for off-line tests when
its control cable was
disconnected and/or REG/BAT
fuse was removed. When cable
and fuse are restored, rectifier
operates in remote sensing
mode and output voltage is
lowered.
Advance the OUTPUT VOLT
ADJ control clockwise to
compensate.
Table 7-A: Troubleshooting
Problem
Probable Cause
Probable Corrective Action
Содержание Lineage 2000 J85503B-2